2018-12-27 17:08:46PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 PROVIDE CLARIFICATION FOR THE FOLLOWING:
  
 1. CLARIFY THE SCOPE OF WORK IN M-BATH. A. VANITY. B.
 WC. C. SHOWER.
  
 2. ARCH. FLOOR PLAN STATES EXISTING BUT SHOWS TANKLESS
 WATER HEATER LOCATED AT EXTERIOR WALL OF M-BATH. NOTE
 STATES WH WILL BE LOCATED BACK TO BACK OF OLD WH THAT
 WAS LOCATED IN KITCHEN. PLEASE CLARIFY.
  
 3. SHOW WATER CLOSETS ON PLAN.
  
 4. WHAT SIZE SANITARY SERVICES THE WC ON ISOMETRIC
 DRAWING?
  
 5. PROVIDE DEMENSIONS IN BATHROOMS TO VERIFY REQUIRED
 CLEARANCES.
  
 6. ARE BOTH SYSTEMS TIED TO BLDG. DRAIN OR BLDG. SEWER?
 IF SEPERATE SYSTEMS ARE TIED TO BLDG. SEWER THEN A
 SECOND VTR WILL BE REQUIRED.
  
 7. NOTE ON ELECTRICAL PLAN STATES RE-LOCATE WASHER AND
 DRYER. WHERE WILL THEY BE LOCATED?
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  