2018-12-21 16:34:23 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18110877 |
| REVIEWED: DECEMBER 21, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC EXISTING 504.1]STATE THE LEVEL OF ALTERATION |
| FOR WORK BEING PERFORMED. THIS LOOKS A LEVEL 2 |
| ALTERATION SINCE WALLS ARE BEING REMOVED. |
| |
| 2. [FBC AMENDED 107.3.5] |
| PROVIDE DESIGN DATA FOR OPENINGS |
| WIND SPEED V ULT = (170) |
| WIND SPEED V ASD = (132) |
| EXPOSURE CATEGORY = B |
| BUILDING CLASSIFICATION = ENCLOSED |
| MEAN BLDG. HGT. = ? |
| PLEASE PROVIDE AN OPENING SCHEDULE TO SHOW THE SIZES |
| AND DESIGN PRESSURES. |
| PRESSURES CAN BE USED FROM R301.2(2) WALL ZONE 4 OR 5 |
| AS APPROPRIATE. |
| |
| 3. [FBC AMENDED 107.3.5]PROVIDE IN-FILL DETAIL WHERE |
| CMU WALL IS BEING CLOSED UP. INCLUDE EXTERIOR FINISH, |
| DOWELS AND INTERIOR INSULATION/FINISH. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |