Plan Review Notes
Plan Review Notes For Permit 18110877
Permit Number 18110877
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-21 16:34:23****CORRECTIONS****
 W.P.B. PERMIT: 18110877
 REVIEWED: DECEMBER 21, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC EXISTING 504.1]STATE THE LEVEL OF ALTERATION
 FOR WORK BEING PERFORMED. THIS LOOKS A LEVEL 2
 ALTERATION SINCE WALLS ARE BEING REMOVED.
  
 2. [FBC AMENDED 107.3.5]
 PROVIDE DESIGN DATA FOR OPENINGS
 WIND SPEED V ULT = (170)
 WIND SPEED V ASD = (132)
 EXPOSURE CATEGORY = B
 BUILDING CLASSIFICATION = ENCLOSED
 MEAN BLDG. HGT. = ?
 PLEASE PROVIDE AN OPENING SCHEDULE TO SHOW THE SIZES
 AND DESIGN PRESSURES.
 PRESSURES CAN BE USED FROM R301.2(2) WALL ZONE 4 OR 5
 AS APPROPRIATE.
  
 3. [FBC AMENDED 107.3.5]PROVIDE IN-FILL DETAIL WHERE
 CMU WALL IS BEING CLOSED UP. INCLUDE EXTERIOR FINISH,
 DOWELS AND INTERIOR INSULATION/FINISH.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  