2018-12-20 17:24:34 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | JOSEAN A. DUPREY | | PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6716 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. THE EXISTING SHALL COMPLY WITH THE BARRIER EDGE | | PROTECTION. | | FCB ACCESSIBILITY 405.9.2 A CURB OR BARRIER SHALL BE | | PROVIDED THAT PREVENTS THE PASSAGE OF A 4 INCH DIAMETER | | SPHERE, WHERE ANY PORTION OF THE SPHERE IS WITHIN 4 | | INCHES OF THE FINISH FLOOR OR GROUND SURFACE. | | | | 2. THE SLOPE FOR THE PROPOSED RAMP WAS NOT PROVIDE. THE | | PROPOSED RAMP IS A MEANS OF EGRESS ACCESS ROUTE AND | | MUST MEET THE REQUIREMENTS OF FBC 1012.2. | | FBC 1012.2 RAMPS USED AS PART OF A MEANS OF EGRESS | | SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN ONE UNIT | | VERTICAL IN 12 UNITS HORIZONTAL (8-PERCENT SLOPE). THE | | SLOPE OF OTHER PEDESTRIAN RAMPS SHALL NOT BE STEEPER | | THAN ONE UNIT VERTICAL IN EIGHT UNITS HORIZONTAL | | (12.5-PERCENT SLOPE). | | | | 3. THE RESTRIPE APPEARS TO BE DONE WITHOUT PERMIT. | | PLEASE PROVIDE PERMIT NUMBER FOR PARKING LOT RESTRIPE. | | FBC 107 | | | | 4.PLEASE ADDRESS THE FIRST REVIEW COMMENTS. | | |
|