Plan Review Notes For Permit 18110768 |
Permit Number |
18110768 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2019-04-15 08:50:17 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561?805?6673 | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | APPROVED WITH PROVISOS: | | | | 1. OK | | 2. OK | | 3. OK PER RED?LINED PLANS. FBC R 322.2.2.1 THE FLOOD | | VENTS NEED TO BE INSTALLED ON DIFFERENT SIDES. | | 4. OK | | 5. OK A SEPERATE PERMIT IS REQUIRED FOR THE POOL. | | 6. OK A SEPERATE PERMIT IS REQUIRED FOR THE GENERATOR. | | 7. OK WITH PROVISO THE PRODUCT APPROVALS FOR WINDOWS | | AND DOORS WILL BE REQUIRED PRIOR TO INSPECTION. | | 8. OK | | 9. OK |
|