2018-12-07 12:41:50 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE |
| OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING |
| UNIT. NEC 210.52(E)(3); FBC RE E3901.7 |
| 2. RISER DIAGRAM SHOWS THE FEED TO THE GENERATOR WITH A |
| #10 EQUIPMENT GROUNDING CONDUCTOR. THIS IS NOT THE |
| CORRECT SIZE FOR A FEED WITH A 125 AMP BREAKER ON |
| GENERATOR AS SHOWN. PROVIDE CORRECTION. NEC 250.122; |
| FBC RE E3704.6 |
| 3. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM |
| BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET |
| FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE |
| R314.3(4), NFPA 72:29.8.3.4 |
| 4. THERE ARE 3 LIGHTS SHOWN OUTSIDE THAT APPEAR TO BE |
| IN THE POOL, SWITCHED FROM INSIDE THE HOUSE. ARE THESE |
| IN FACT POOL LIGHTS, RATED TO BE IN THE POOL, OR IS |
| THIS SOMETHING THAT WILL BE MOUNTED ABOVE THE POOL? |
| PROVIDE CLARIFICATION AND COMPLIANCE WITH FBC RE E4203 |
| IF NECESSARY. WPB FBC 107.2.1; NEC 680.22; FBC RE |
| E4203.4 |
| 5. BASED ON THE OUTLINE OF POOL SHOWN ON PLAN, THERE |
| ARE GFCI RECEPTACLES THAT ARE TOO CLOSE TO THE POOL |
| WATER. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC |
| 680.22; FBC RE E4203.1 |
| 6. ALL GROUNDING ELECTRODES PRESENT MUST BE BONDED |
| TOGETHER. THE CONCRETE ENCASED ELECTRODE IS NOT SHOWN |
| ON RISER DIAGRAM. PROVIDE CORRECTION. NEC 250.52; FBC |
| RE E3608.1 |
| 7. ALL RECEPTACLE OUTLETS IN BATHROOM MUST BE GFCI |
| PROTECTED. PROVIDE CORRECTION FOR MASTER BATH TOILET |
| AREA. NEC 210.8; FBC RE E3902.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |