Plan Review Notes
Plan Review Notes For Permit 18110758
Permit Number 18110758
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-07 14:23:34NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 SEC. R401.3 FBC_RESIDENTIAL:
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. IN THE CASE OF
 DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE
 DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING
 STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE
 SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO
 WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN
 THE APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR
 OR WHEN OTHERWISE WARRANTED.
  
 SEC. 110.9 CITY AMENDMENTS: IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS
 OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
 CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY
 PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE
 DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION,
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A
 LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE
 INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE FINAL
 INSPECTION.
  
 2- IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 3- SITE PLAN SHOWN ON SHEET AS-1 AND SURVEY SUBMITTED
 DON'T MATCH. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 3- A)SURVEY NEEDS TO SPECIFY WHAT REFERENCE WAS USED TO
 DETERMINE THE ELEVATIONS. NORTH AMERICAN VERTICAL DATUM
 OF 1988?. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) PROVIDE SURVEY WITH SURVEYORS ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. OR SUBMIT
 SURVEY WITH DIGITAL SIGNATURE.
  
 4- REVISE ENERGY CALCULATIONS:
 A)WALL INSULATION DOESN'T MATCH PLANS.
  
 B)PROVIDE THE NAME OF THE OWNER. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) PROVIDE THE NAME OF THE PERSON PERFORMING THE ENERGY
 CALCULATIONS. REVISE AS REQUIRED. SEC. R405.4.2.1
 FBC-ENERGY CONSERVATION.
  
 D) IT LOOKS LIKE THE NUMBER OF PEOPLE (10 PEOPLE) IS
 NOT CORRECT AND IS A LITTLE BIT HIGH FOR A SINGLE
 FAMILY RESIDENCE OF 4 BEDROOMS. REVISE THE NUMBER OF
 OCCUPANTS OR PROVIDE JUSTIFICATIONS OF WHY CONSIDERING
 10 PEOPLE IN THESE CALCULATIONS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) EXTERIOR DOORS ORIENTATION DOESN'T MATCH PLANS. EVEN
 IF DOING CALCULATIONS FOR WORST CASE SCENARIO. REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)WINDOWS INFORMATION IS INCORRECT. REVISE THE WINDOW
 ORIENTATION (WORST CASE SCENARIO), WINDOW AREA AND
 WINDOW OVERHANG SEPARATION TO MATCH PLANS. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) PROVIDE MANUFACTURER'S INFORMATION SHOWING THE
 WINDOWS EFFICIENCIES SPECIFIED ON THE FIRST PAGE OF THE
 ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS WILL BE REQUIRED
 FOR INSPECTION.
  
 5- UNABLE TO SEE SOIL TEST REPORT. IT WAS NOT UPLOADED.
 PROVIDE SOIL TEST REPORT. SEC. R401.4 FBC-RESIDENTIAL.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 7- VALUATION DECLARED IN THE PERMIT APPLICATION WAS
 UPDATED TO $179,082 AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. THE PERMIT FEE BALANCE IS $1,734.60.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]