Plan Review Notes
Plan Review Notes For Permit 18110671
Permit Number 18110671
Review Stop P
Sequence Number 4
Notes
Date Text
2019-05-02 14:20:30PLUMBING 4TH REVIEW**DENIED**FL ST 553.80 (B)2B WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) ANSWERED
  
 2) 3RD REQUEST .PROVIDE CLEAR FLOOR SPACE ON SHT. A-1
 FOR 1 OF THE 2 LOBBY HAND SINKS, . FBC-A 212.2, 606
  
 3) 3RD REQUEST .PROVIDE CLEAR FLOOR SPACE FOR THE
 DRINKING FOUNTAIN ON SHT. A-1 FBC 107.3.5
  
 4) 3RD REQUEST. PROVIDE INSTALLATION MANUAL FOR THE
 LINT INTERCEPTOR. FBC 107.2.1
  
 5) ANSWERED
  
 6) ANSWERED
  
 7) 3RD REQUEST. NO RESPONSE PROVIDED NO INSTALLATION
 MANUALS PROVIDED. PROVIDE PEDICURE CHAIRS SPEC SHEETS
 AND INSTALLATION MANUAL'S. FBC 107.3.5
  
 8) 2ND REQUEST. SHT P-1 IIS NOW SEALED BUT STILL NOT
 SIGNED . FAC 61G15-23.001
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR