2019-05-02 14:20:30 | PLUMBING 4TH REVIEW**DENIED**FL ST 553.80 (B)2B WITH |
| RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| |
| 1) ANSWERED |
| |
| 2) 3RD REQUEST .PROVIDE CLEAR FLOOR SPACE ON SHT. A-1 |
| FOR 1 OF THE 2 LOBBY HAND SINKS, . FBC-A 212.2, 606 |
| |
| 3) 3RD REQUEST .PROVIDE CLEAR FLOOR SPACE FOR THE |
| DRINKING FOUNTAIN ON SHT. A-1 FBC 107.3.5 |
| |
| 4) 3RD REQUEST. PROVIDE INSTALLATION MANUAL FOR THE |
| LINT INTERCEPTOR. FBC 107.2.1 |
| |
| 5) ANSWERED |
| |
| 6) ANSWERED |
| |
| 7) 3RD REQUEST. NO RESPONSE PROVIDED NO INSTALLATION |
| MANUALS PROVIDED. PROVIDE PEDICURE CHAIRS SPEC SHEETS |
| AND INSTALLATION MANUAL'S. FBC 107.3.5 |
| |
| 8) 2ND REQUEST. SHT P-1 IIS NOW SEALED BUT STILL NOT |
| SIGNED . FAC 61G15-23.001 |
| |
| |