Plan Review Notes For Permit 18110671 |
Permit Number |
18110671 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-04-29 17:57:38 | PLUMBING 3RD REVIEW**DENIED** | | | | 1) ANSWERED | | | | 2) 2ND REQUEST PARTIAL ANSWER.PROVIDE CLEAR FLOOR SPACE | | ON SHT. A-1 FOR 1 OF THE 2 LOBBY HAND SINKS, . FBC-A | | 212.2, 606 | | | | 3) 2ND REQUEST PARTIAL ANSWER.PROVIDE CLEAR FLOOR SPACE | | FOR THE DRINKING FOUNTAIN ON SHT. A-1 FBC 107.3.5 | | | | 4) PARTIAL ANSWERED. PROVIDE INSTALLATION MANUAL FOR | | THE LINT INTERCEPTOR. FBC 107.2.1 | | | | 5) 2ND REQUEST PARTIAL ANSWER. ALL NOTES ARE NOW | | MISSING. SHOW THE RELIEF LINE FOR THE WATER HEATER | | DISCHARGING INTO THE ROOM/ HEATER PAN/ PIPE SIZING. | | FBC-P 504.6. PROVIDE HOW THE PAN DRAIN IS GOING TO BE | | RAN OUTSIDE AND TERMINATE MIN 6" ABOVE GRADE. FBC-P | | 504.7, 504.7.1, 504.7.2 | | | | 6) ANSWERED BUT ALL PIPE SIZING IS MISSING FOR BOTH | | SANITARY AND WATER ISOMETRIC. FBC 107.3.5 | | | | 7) 2ND REQUEST. NO RESPONSE PROVIDED NO INSTALLATION | | MANUALS PROVIDED. PROVIDE PEDICURE CHAIRS SPEC SHEETS | | AND INSTALLATION MANUAL'S. FBC 107.3.5 | | | | | | NEW COMMENT: | | | | 1) SHT P-1 IS NOT SIGNED AND SEALED. SHT P-2 IS NOT | | SEALED . FAC 61G15-23.001 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | [email protected] |
|