Plan Review Notes
Plan Review Notes For Permit 18110671
Permit Number 18110671
Review Stop P
Sequence Number 2
Notes
Date Text
2019-04-08 15:20:57PLUMBING 2ND REVIEW**DENIED**
  
 1) BEING THAT THIS IS A CHANGE OF OCCUPANCY BOTH THE
 EXISTING RESTRROOMS SHALL COMPLY WITH 2017 FBC PLUMBING
 AND ACCESSIBILITY. THE RESTROOMS MUST FULLY COMPLY AND
 BE PART OF THE INSPECTIONS. FBC 107.3.5
  
 2) PROVIDE CLEAR FLOOR SPACE AND CABINET HEIGHT FOR 1
 OF THE 2 HAND SINKS. FBC-A 212.2, 606
  
 3) SHT P-1 CALLS OUT THE DRINKING FOUNTAIN IS EXISTING.
 PERMIT # 17060769 AND FINAL REVISION #18019865 DO NOT
 SHOW A DRINKING FOUNTAIN, PROVIDE CLEAR FLOOR SPACE AND
 MOUNTING HEIGHT DETAILS. FBC 107.3.5
  
 4) SHT P-1 LITE FILTER DOES NOT MEET THE INTENT OF THE
 CODE FBC-P 1003.1. PROVIDE A LIT INTERCEPTOR AND THE
 COMPLETE INSTALLATION MANUAL. FBC -P 1003.6.
  
 5) SHOW THE RELIEF LINE FOR THE WATER HEATER
 DISCHARGING INTO THE ROOM/ HEATER PAN. FBC-P 504.6.
 PROVIDE HOW THE PAN DRAIN IS GOING TO BE RAN OUTSIDE
 AND TERMINATE MIN 6" ABOVE GRADE. FBC-P 504.7, 504.7.1,
 504.7.2
  
 6) PLUMBING ISOMETRIC AND FLAT DRAWING DOERS NOT SHOW
 EITHER GROUP OF PEDICURE CHAIRS AS VENTED. PROVIDE
 ISOMETRIC AND FLAT DRAWING PROPERLY VENTED ALL FIXTURES
 FBC-P 901.2.1.
  
 7) PROVIDE PEDICURE CHARIS SPEC SHEETS AND INSTALLATION
 MANUAL'S. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  