2018-12-13 12:05:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18110671 |
| 12/14/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-2: AN ENERGY RECOVERY VENTILATOR IS REQUIRED |
| FOR THE NAIL SALON EXHAUST SYSTEM IN COMPLIANCE WITH |
| SECTION C403.2.7 FBC EC. PLEASE CORRECT THE PLANS AND |
| CALCULATIONS ACCORDINGLY. |
| |
| 2) M-2: REFER TO TABLE 403.3.1.1 AND FOOTNOTE H UNDER |
| THE TABLE AND PROVIDE AN EXHAUST VENTILATION |
| CALCULATION FOR THE PROPOSED SPACE AT THE REQUIRED RATE |
| OF 0.60 CFMS PER SF. PLEASE NOTE THE FOLLOWING: A) THE |
| CURRENT EXHAUST SYSTEM INDICATED AT 1000 CFRMS DOES NOT |
| MEET THE REQUIRED 0.60 CFMS PER SF RATE REQUIRED RATE |
| SO ADDITIONAL EXHAUST MUST BE PROVIDED. B) IT IS |
| REQUIRED THAT THE EXHAUST SYSTEM RUN CONTINOULSY DURING |
| OCCUPANCY HOWEVER THE SEQUENCE OF OPERATION FOR THE |
| SYSTEM HAS NOT BEEN ADDRESSED ON THE PLANS- SEE SECTION |
| 501.4 FBC M. PLEASE NOTE THAT INSTALLATION OF THE ERV |
| MAY RESOLVE THIS ISSUE BECAUSE IT WILL HAVE TO BE |
| CONNECTED TO THE AC SYSTEM. |
| |
| 3) M-1, M-2: BASED ON THE NUMBER OF PEDICURE CHAIRS, IT |
| APPEARS THAT THE 38 PERSON OCCUPANT LOAD WHICH IS SHOWN |
| ON THE LIFE SAFETY PLANS AND THE O/A TABLE IS |
| INCORRECT. PEDICURE CHAIRS WERE COUNTED AS ONE |
| OCCUPANT, HOWEVER THE CHEMICAL APPLICATOR AT EACH CHAIR |
| WAS NOT COUNTED. |
| |
| 4) M-1: REFER TO TABLE 403.3.1.1 FOOTNOTE B: THE PLAN |
| SHOWS RECIRCULATION OF AIR FROM THE SALON TO THE |
| BREAKROOM, FACIAL ROOM, AND THE TOILET ROOMS WHICH IS |
| PROHIBITED. |
| |
| 5) M-2: CLARIFY HOW THE SOURCE CAPTURE SYSTEM FOR THE |
| PEDICURE CHAIRS WILL BE IN COMPLIANCE WITH SECTION |
| 502.20 WHICH REQUIRES THE EXHAUST INLET TO BE LOCATED |
| NOT MORE THAN 12 INCHES HORIZONTALLY AND VERTICALLY |
| FROM THE POINT OF CHEMICAL APPLICATION. THE CURRENT |
| PLAN AND DETAILS INDICATE THE INLETS ON THE FLOOR UNDER |
| THE CHAIRS. |
| |
| 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER |
| PER SECTION 504.1 FBC M. A) INDICATE THE TOTAL RUN |
| LENGTH OF THE DRYER VENT- SECTION 504.8.4. B) PLEASE |
| NOTE THAT MAKEUP AIR MAY BE REQUIRED- SECTION 504.6. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |