Plan Review Notes
Plan Review Notes For Permit 18110671
Permit Number 18110671
Review Stop M
Sequence Number 1
Notes
Date Text
2018-12-13 12:05:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110671
 12/14/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2: AN ENERGY RECOVERY VENTILATOR IS REQUIRED
 FOR THE NAIL SALON EXHAUST SYSTEM IN COMPLIANCE WITH
 SECTION C403.2.7 FBC EC. PLEASE CORRECT THE PLANS AND
 CALCULATIONS ACCORDINGLY.
  
 2) M-2: REFER TO TABLE 403.3.1.1 AND FOOTNOTE H UNDER
 THE TABLE AND PROVIDE AN EXHAUST VENTILATION
 CALCULATION FOR THE PROPOSED SPACE AT THE REQUIRED RATE
 OF 0.60 CFMS PER SF. PLEASE NOTE THE FOLLOWING: A) THE
 CURRENT EXHAUST SYSTEM INDICATED AT 1000 CFRMS DOES NOT
 MEET THE REQUIRED 0.60 CFMS PER SF RATE REQUIRED RATE
 SO ADDITIONAL EXHAUST MUST BE PROVIDED. B) IT IS
 REQUIRED THAT THE EXHAUST SYSTEM RUN CONTINOULSY DURING
 OCCUPANCY HOWEVER THE SEQUENCE OF OPERATION FOR THE
 SYSTEM HAS NOT BEEN ADDRESSED ON THE PLANS- SEE SECTION
 501.4 FBC M. PLEASE NOTE THAT INSTALLATION OF THE ERV
 MAY RESOLVE THIS ISSUE BECAUSE IT WILL HAVE TO BE
 CONNECTED TO THE AC SYSTEM.
  
 3) M-1, M-2: BASED ON THE NUMBER OF PEDICURE CHAIRS, IT
 APPEARS THAT THE 38 PERSON OCCUPANT LOAD WHICH IS SHOWN
 ON THE LIFE SAFETY PLANS AND THE O/A TABLE IS
 INCORRECT. PEDICURE CHAIRS WERE COUNTED AS ONE
 OCCUPANT, HOWEVER THE CHEMICAL APPLICATOR AT EACH CHAIR
 WAS NOT COUNTED.
  
 4) M-1: REFER TO TABLE 403.3.1.1 FOOTNOTE B: THE PLAN
 SHOWS RECIRCULATION OF AIR FROM THE SALON TO THE
 BREAKROOM, FACIAL ROOM, AND THE TOILET ROOMS WHICH IS
 PROHIBITED.
  
 5) M-2: CLARIFY HOW THE SOURCE CAPTURE SYSTEM FOR THE
 PEDICURE CHAIRS WILL BE IN COMPLIANCE WITH SECTION
 502.20 WHICH REQUIRES THE EXHAUST INLET TO BE LOCATED
 NOT MORE THAN 12 INCHES HORIZONTALLY AND VERTICALLY
 FROM THE POINT OF CHEMICAL APPLICATION. THE CURRENT
 PLAN AND DETAILS INDICATE THE INLETS ON THE FLOOR UNDER
 THE CHAIRS.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER
 PER SECTION 504.1 FBC M. A) INDICATE THE TOTAL RUN
 LENGTH OF THE DRYER VENT- SECTION 504.8.4. B) PLEASE
 NOTE THAT MAKEUP AIR MAY BE REQUIRED- SECTION 504.6.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  