Date Text
2019-01-10 10:25:581ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE ADDRESS ON THE PLAN SHEETS IS 221 EDGEWOOD DR
 THIS IS INCORRECT THAT ADDRESS DOES NOT EXIST THE
 PERMIT APPLICATION STATES THE ADDRESS AS 215 PLEASE
 CORRECT ON PLAN SHEETS. PER FBC AMEND TO FBC 107.2.1
 2. I COULD NOT LOCATE THE MASTER BUILDING PERMIT
 APPLICATION IT APPEARS THAT IT DID NOT GET UPLOADED
 PLEASE CLARIFY. PER FBC AMEND TO FBC 107.2.1
 3. A CLEAN OUT IS REQUIRED ANY BRANCH OF THE BUILDING
 DRAIN EXISTS THE BUILDING AND CONNECTS TO THE BUILDING
 SEWER PLEASE SHOW ON ISOMETRIC DRAWING. PER FBC RES
 P3005.2.3
 4. PLEASE PLACE NOTE ON THE PLANS. [THE SHUT OF VALVES
 FOR THE STACKABLE WASHING MACHINE SHALL BE ACCESSIBLE
 PER FBC RES P2903.9.3] [THE WATER HEATER AND PIPING
 SHALL COMPLY WITH THE FBC ENERGY R403.5]
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  