2018-12-06 16:41:19 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| |
| OUTLETS NEEDED AT THE FRONT AND REAR OF STRUCTURE. |
| E3901.7 OUTDOOR OUTLETS. |
| NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM |
| INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE |
| RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE |
| BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE |
| LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE |
| THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)] |
| |
| STRUCTURE SHALL HAVE A GROUNDING SYSTEM INSTALLED PER |
| E3607.3 |
| E3607.3 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) |
| OR BRANCH CIRCUIT(S). |
| BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH |
| CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR |
| GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH |
| SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S) |
| SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION |
| E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS |
| ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING |
| GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) |
| REQUIRED IN SECTION E3608 SHALL BE INSTALLED. |
| [250.32(A)] |
| |
| MAINS NEED TO BE GROUPED |
| E3601.6 SERVICE DISCONNECT REQUIRED. |
| MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN |
| A BUILDING OR OTHER STRUCTURE FROM THE SERVICE ENTRANCE |
| CONDUCTORS. (230.70) |
| |
| SMOKE ALARMS |
| R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| EXCEPTIONS: |
| 1.WORK INVOLVING THE EXTERIOR SURFACES OF DWELLINGS, |
| SUCH AS THE REPLACEMENT OF ROOFING OR SIDING, THE |
| ADDITION OR REPLACEMENT OF WINDOWS OR DOORS, OR THE |
| ADDITION OF A PORCH OR DECK, ARE EXEMPT FROM THE |
| REQUIREMENTS OF THIS SECTION. |
| 2.INSTALLATION, ALTERATION OR REPAIRS OF PLUMBING OR |
| MECHANICAL SYSTEMS ARE EXEMPT FROM THE REQUIREMENTS OF |
| THIS SECTION |