Plan Review Notes
Plan Review Notes For Permit 18110627
Permit Number 18110627
Review Stop E
Sequence Number 1
Notes
Date Text
2018-12-06 16:41:19FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 OUTLETS NEEDED AT THE FRONT AND REAR OF STRUCTURE.
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
 BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM
 INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE
 THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)]
  
 STRUCTURE SHALL HAVE A GROUNDING SYSTEM INSTALLED PER
 E3607.3
 E3607.3 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S)
 OR BRANCH CIRCUIT(S).
 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH
 CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH
 SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S)
 SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION
 E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS
 ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S)
 REQUIRED IN SECTION E3608 SHALL BE INSTALLED.
 [250.32(A)]
  
 MAINS NEED TO BE GROUPED
 E3601.6 SERVICE DISCONNECT REQUIRED.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE ENTRANCE
 CONDUCTORS. (230.70)
  
 SMOKE ALARMS
 R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 EXCEPTIONS:
 1.WORK INVOLVING THE EXTERIOR SURFACES OF DWELLINGS,
 SUCH AS THE REPLACEMENT OF ROOFING OR SIDING, THE
 ADDITION OR REPLACEMENT OF WINDOWS OR DOORS, OR THE
 ADDITION OF A PORCH OR DECK, ARE EXEMPT FROM THE
 REQUIREMENTS OF THIS SECTION.
 2.INSTALLATION, ALTERATION OR REPAIRS OF PLUMBING OR
 MECHANICAL SYSTEMS ARE EXEMPT FROM THE REQUIREMENTS OF
 THIS SECTION