Plan Review Notes
Plan Review Notes For Permit 18110627
Permit Number 18110627
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-31 09:07:43****CORRECTIONS****
 W.P.B. PERMIT: 18110627
 REVIEWED: DECEMBER 28, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 THE ENERGY CALCULATIONS IN SUPPORTING DOCUMENTS IS LOAD
 CALCS ONLY. PLEASE PROVIDE ADDITIONAL CALCULATIOND TO
 INCLUDE DATA USED TO DETERMINE HVAC LOAD CALCULATIONS.
  
 2. [FBC AMENDED 107.2.1.2]PROVIDE STAIRCASE AND GUARD
 RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED.
  
 3. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 DOOR 101 103 AND 104, OR INDICATE THAT YOU WOULD LIKE
 IT DEFERED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  