2018-12-31 09:07:43 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18110627 |
| REVIEWED: DECEMBER 28, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO |
| MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. |
| CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION. |
| THE ENERGY CALCULATIONS IN SUPPORTING DOCUMENTS IS LOAD |
| CALCS ONLY. PLEASE PROVIDE ADDITIONAL CALCULATIOND TO |
| INCLUDE DATA USED TO DETERMINE HVAC LOAD CALCULATIONS. |
| |
| 2. [FBC AMENDED 107.2.1.2]PROVIDE STAIRCASE AND GUARD |
| RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED. |
| |
| 3. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR |
| DOOR 101 103 AND 104, OR INDICATE THAT YOU WOULD LIKE |
| IT DEFERED. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |