Plan Review Notes
Plan Review Notes For Permit 18110485
Permit Number 18110485
Review Stop B
Sequence Number 1
Notes
Date Text
2018-11-30 07:38:41****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 1. DESIGN PROFESSIONAL'S (ENGINEER) SIGNATURE & SEAL
 ARE MISSING FROM PLANS.
 2. THE CONCRETE FOOTINGS AND PAD ARE MISSING DIMENSIONS
 AND REINFORCEMENT/CRACK PREVENTION INFORMATION.
 3. THE STRUCTURAL CONNECTIONS ARE NOT COMPLETE :
 A. A.W.S SECTION/CLAUSE 3.1 PROVIDE A WELD PROCEDURE
 SPECIFICATION FOR WELDED CONNECTIONS.
 B. A.W.S SECTION/CLAUSE 4.2.2 PROVIDE WELDERS
 PERFORMANCE QUALIFICATION RECORD FOR THE WELDING
 PERSONNEL.
 C. IN THE CASE THAT SOME OF THE DESCRIBED WELD
 CONNECTIONS ARE TO BE BOLTED AND/OR SCREWED, PROVIDE
 DETAILS.