Plan Review Notes For Permit 18110485 |
Permit Number |
18110485 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-11-30 07:38:41 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | 1. DESIGN PROFESSIONAL'S (ENGINEER) SIGNATURE & SEAL | | ARE MISSING FROM PLANS. | | 2. THE CONCRETE FOOTINGS AND PAD ARE MISSING DIMENSIONS | | AND REINFORCEMENT/CRACK PREVENTION INFORMATION. | | 3. THE STRUCTURAL CONNECTIONS ARE NOT COMPLETE : | | A. A.W.S SECTION/CLAUSE 3.1 PROVIDE A WELD PROCEDURE | | SPECIFICATION FOR WELDED CONNECTIONS. | | B. A.W.S SECTION/CLAUSE 4.2.2 PROVIDE WELDERS | | PERFORMANCE QUALIFICATION RECORD FOR THE WELDING | | PERSONNEL. | | C. IN THE CASE THAT SOME OF THE DESCRIBED WELD | | CONNECTIONS ARE TO BE BOLTED AND/OR SCREWED, PROVIDE | | DETAILS. |
|