Plan Review Notes For Permit 18110470 |
Permit Number |
18110470 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-11-14 15:19:39 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SYSTEM #4 THAT IS MARKED ON THE UL DIRECTORY DOES | | NOT MATCH THE MIAMI DADE NOA NO. 18-0807.18 THAT WAS | | SUBMITTED. THE UL DIRECTORY HAS LPA3000H FOAM AND | | THERM-O-FLEX ELASTOMERIC ROOF COATING FOR THE BASE AND | | TOP COATS. FBC 2603.6 | | | | 2) SUBMIT TWO SETS OF THE MIAMI-DADE COUNTY NOA FOR THE | | PROTECTIVE ROOF COATING THAT WILL BE USED. SEE PAGE 4 | | OF NOA NO. 18-0807.18. |
|