2019-01-18 11:30:27****CORRECTIONS****
 W.P.B. PERMIT: 18110465
 REVIEWED: JANUARY 16, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. 107.3.5 FBC[AMENDED] INDEX DOESN?T MATCH CIVIL PLAN
 UPLOADED.
 PLEASE UPDATE INDEX TO MATCH THREE SHEETS PROVIDED FOR
 CIVIL.
 ALSO, MECHANICAL SHEETS AS NEEDED FOR MECHANICAL REVIEW
 COMMENTS.
  
 2. 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3 AS SELECTED BY THE APPLICANT. SECTIONS 301.1.1
 THROUGH 301.1.3 SHALL NOT BE APPLIED IN COMBINATION
 WITH EACH OTHER.
 -WHICH METHOD IS BEING USED FOR COMPLIANCE? PLEASE ADD
 TO COVER SHEET DATA(PRESCRIPTIVE,WORK AREA OR
 PERFORMANCE)
  
 3. 107.5.3 FBC[AMENDED] IS THE BUILDING SPRINKLERED OR
 NON SPRINKLERED?
 -PLEASE PROVIDE NOTE IN COVER SHEET DATA.
  
 4. 206.1 FBC[A] GENERAL. ACCESSIBLE ROUTE.
 SHOW ACCESSIBLE ROUTE FROM PARKING TO ACCESSIBLE ENTRY.
  
 5. 1012.2 FBC[B] SLOPE. RAMPS USED AS PART OF A MEANS
 OF EGRESS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN
 ONE UNIT VERTICAL IN 12 UNITS HORIZONTAL (8-PERCENT
 SLOPE).
 PLEASE ADD SLOPE INDICATION ON RAMP.
 ALSO, ADD DIMENSIONS TO RAMP.
  
 6. 1012.6.1 FBC[B] SLOPE. LANDINGS SHALL HAVE A SLOPE
 NOT STEEPER THAN ONE UNIT VERTICAL IN 48 UNITS
 HORIZONTAL (2-PERCENT SLOPE) IN ANY DIRECTION. CHANGES
 IN LEVEL ARE NOT PERMITTED.
 -ADD SLOPE INDICATION ON RAMP LANDINGS.
  
 7. 1012.10 FBC[B] EDGE PROTECTION. EDGE PROTECTION
 COMPLYING WITH SECTION 1012.10.1 OR 1012.10.2 SHALL BE
 PROVIDED ON EACH SIDE OF RAMP RUNS AND AT EACH SIDE OF
 RAMP LANDINGS. (SEE EXCEPTIONS)
 PROVIDE CROSS SECTION OF RAMP TO SHOW HOW EDGE
 PROTECTION IS ACHIEVED.
  
 8. 107.2.1.2 FBC[AMENDED] PROVIDE GUARD RAIL
 ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED.
  
 9. 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE
 ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED.
  
 10. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR WINDOWS AND DOORS, OR INDICATE THAT YOU WOULD LIKE
 THEM DEFERED.
 SHEET A5.0 SHOWS ONE PRODUCT APPROVAL NUMBER FOR
 EXTERIOR DOOR FL-16-1206.04.
 A. IF THIS IS BEING USED PLEASE UPLOAD THE PRODUCT
 APPROVAL TO PROJECT DOX SUPPORTING DOCUMENTS.
 B. ARE ANY WINDOWS BEING REPLACED, OR ARE THEY JUST TO
 BE COVERED. PLEASE PROVIDE ANY APPLICABLE PRODUCT
 APPROVALS IN SUPPORTING DOCUMENTS.
 11. 1014.6 FBC[B] HANDRAIL EXTENSIONS. HANDRAILS SHALL
 RETURN TO A WALL, GUARD OR THE WALKING SURFACE OR SHALL
 BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT FLIGHT OF
 STAIRS OR RAMP RUN. WHERE HANDRAILS ARE NOT CONTINUOUS
 BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) BEYOND
 THE TOP RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF
 ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS WHERE
 HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE
 SAME DIRECTION OF THE FLIGHTS OF STAIRS AT STAIRWAYS
 AND THE RAMP RUNS AT RAMPS. (SEE 1415.6 FOR EXCEPTIONS
 AND REQUIREMENTS)
 -REVIEW HANDRAIL EXTENSIONS AT NEW STAGE STAIRS.
  
 12. 407.1 FBC[A] GENERAL. ELEVATORS SHALL COMPLY WITH
 407 AND WITH ASME A17.1 (INCORPORATED BY REFERENCE, SEE
 ?REFERENCED STANDARDS? IN CHAPTER 1). THEY SHALL BE
 PASSENGER ELEVATORS AS CLASSIFIED BY ASME A17.1.
 ELEVATOR OPERATION SHALL BE AUTOMATIC.
  
 13. 1003.7 FBC[B] ELEVATORS, ESCALATORS AND MOVING
 WALKS. ELEVATORS, ESCALATORS AND MOVING WALKS SHALL NOT
 BE USED AS A COMPONENT OF A REQUIRED MEANS OF EGRESS
 FROM ANY OTHER PART OF THE BUILDING. EXCEPTION:
 ELEVATORS USED AS AN ACCESSIBLE MEANS OF EGRESS IN
 ACCORDANCE WITH SECTION 1009.
  
 14. 2702.2.2 FBC[B] ELEVATORS AND PLATFORM LIFTS.
 STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS AND
 PLATFORM LIFTS AS REQUIRED IN SECTIONS 1009.4, 1009.5,
 3003.1, 3007.8 AND 3008.8.
 IF ELEVATOR IS BEING USED FOR ACCESSIBLE MEANS OF
 EGRESS, HOW IS BACK-UP POWER BEING SUPPLIED?
 OTHERWISE, PLEASE PROVIDE ALTERNATIVE ACCESSIBLE PATH
 OF EGRESS FROM SECOND FLOOR SPACE.
  
 15. 3003.1 FBC[B] STANDBY POWER. IN BUILDINGS AND
 STRUCTURES WHERE STANDBY POWER IS REQUIRED OR FURNISHED
 TO OPERATE AN ELEVATOR, THE OPERATION SHALL BE IN
 ACCORDANCE WITH SECTIONS 3003.1.1 THROUGH 3003.1.4.
  
 16. 407.4.1 FBC[A] CAR DIMENSIONS. INSIDE DIMENSIONS OF
 ELEVATOR CARS AND CLEAR WIDTH OF ELEVATOR DOORS SHALL
 COMPLY WITH TABLE 407.4.1.
 -PLEASE ADD CAB DIMENSIONS AND TURNING SPACE ON PLANS.
  
 17. ASCE 7-10 SECTION 4.5.1 LOADS ON HANDRAIL AND
 GUARDRAIL SYSTEMS.
 -PROVIDE ENGINEERING FOR THE RAIL AT PULPIT, OR
 INDICATE THAT IT WILL BE A DEFERRED SUBMITTAL.
  
 18. 1609.1 FBC[B] APPLICATIONS. BUILDINGS, STRUCTURES
 AND PARTS THEREOF SHALL BE DESIGNED TO WITHSTAND THE
 MINIMUM WIND LOADS PRESCRIBED HEREIN.
 -PLEASE PROVIDE ENGINEERING TO SHOW HOW LEXAN PANELS
 MEET PRESSURES BASED ON SPAN, EDGE DISTANCE AND GLASS
 SEPARATION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -IF ANY SPEC SHEETS OR PRDUCT APPROVALS ARE ADDED,
 PLEASE UPLOAD THEM AS MULTIPAGE FORMAT PDF IN
 SUPPORTING DOCUMENTS.
 -DIGITAL RESUBMITTAL UPON ALL REVIEWS COMPLETED.
  