2019-01-18 11:30:27 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18110465 |
| REVIEWED: JANUARY 16, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| FBC[R] = FBC RESIDENTIAL |
| |
| 1. 107.3.5 FBC[AMENDED] INDEX DOESN?T MATCH CIVIL PLAN |
| UPLOADED. |
| PLEASE UPDATE INDEX TO MATCH THREE SHEETS PROVIDED FOR |
| CIVIL. |
| ALSO, MECHANICAL SHEETS AS NEEDED FOR MECHANICAL REVIEW |
| COMMENTS. |
| |
| 2. 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION, |
| CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| LISTED IN SECTIONS 301.1.1 THROUGH |
| 301.1.3 AS SELECTED BY THE APPLICANT. SECTIONS 301.1.1 |
| THROUGH 301.1.3 SHALL NOT BE APPLIED IN COMBINATION |
| WITH EACH OTHER. |
| -WHICH METHOD IS BEING USED FOR COMPLIANCE? PLEASE ADD |
| TO COVER SHEET DATA(PRESCRIPTIVE,WORK AREA OR |
| PERFORMANCE) |
| |
| 3. 107.5.3 FBC[AMENDED] IS THE BUILDING SPRINKLERED OR |
| NON SPRINKLERED? |
| -PLEASE PROVIDE NOTE IN COVER SHEET DATA. |
| |
| 4. 206.1 FBC[A] GENERAL. ACCESSIBLE ROUTE. |
| SHOW ACCESSIBLE ROUTE FROM PARKING TO ACCESSIBLE ENTRY. |
| |
| 5. 1012.2 FBC[B] SLOPE. RAMPS USED AS PART OF A MEANS |
| OF EGRESS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN |
| ONE UNIT VERTICAL IN 12 UNITS HORIZONTAL (8-PERCENT |
| SLOPE). |
| PLEASE ADD SLOPE INDICATION ON RAMP. |
| ALSO, ADD DIMENSIONS TO RAMP. |
| |
| 6. 1012.6.1 FBC[B] SLOPE. LANDINGS SHALL HAVE A SLOPE |
| NOT STEEPER THAN ONE UNIT VERTICAL IN 48 UNITS |
| HORIZONTAL (2-PERCENT SLOPE) IN ANY DIRECTION. CHANGES |
| IN LEVEL ARE NOT PERMITTED. |
| -ADD SLOPE INDICATION ON RAMP LANDINGS. |
| |
| 7. 1012.10 FBC[B] EDGE PROTECTION. EDGE PROTECTION |
| COMPLYING WITH SECTION 1012.10.1 OR 1012.10.2 SHALL BE |
| PROVIDED ON EACH SIDE OF RAMP RUNS AND AT EACH SIDE OF |
| RAMP LANDINGS. (SEE EXCEPTIONS) |
| PROVIDE CROSS SECTION OF RAMP TO SHOW HOW EDGE |
| PROTECTION IS ACHIEVED. |
| |
| 8. 107.2.1.2 FBC[AMENDED] PROVIDE GUARD RAIL |
| ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED. |
| |
| 9. 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE |
| ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED. |
| |
| 10. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS |
| FOR WINDOWS AND DOORS, OR INDICATE THAT YOU WOULD LIKE |
| THEM DEFERED. |
| SHEET A5.0 SHOWS ONE PRODUCT APPROVAL NUMBER FOR |
| EXTERIOR DOOR FL-16-1206.04. |
| A. IF THIS IS BEING USED PLEASE UPLOAD THE PRODUCT |
| APPROVAL TO PROJECT DOX SUPPORTING DOCUMENTS. |
| B. ARE ANY WINDOWS BEING REPLACED, OR ARE THEY JUST TO |
| BE COVERED. PLEASE PROVIDE ANY APPLICABLE PRODUCT |
| APPROVALS IN SUPPORTING DOCUMENTS. |
| 11. 1014.6 FBC[B] HANDRAIL EXTENSIONS. HANDRAILS SHALL |
| RETURN TO A WALL, GUARD OR THE WALKING SURFACE OR SHALL |
| BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT FLIGHT OF |
| STAIRS OR RAMP RUN. WHERE HANDRAILS ARE NOT CONTINUOUS |
| BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND |
| HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) BEYOND |
| THE TOP RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF |
| ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS WHERE |
| HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE |
| HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING |
| 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF |
| RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE |
| SAME DIRECTION OF THE FLIGHTS OF STAIRS AT STAIRWAYS |
| AND THE RAMP RUNS AT RAMPS. (SEE 1415.6 FOR EXCEPTIONS |
| AND REQUIREMENTS) |
| -REVIEW HANDRAIL EXTENSIONS AT NEW STAGE STAIRS. |
| |
| 12. 407.1 FBC[A] GENERAL. ELEVATORS SHALL COMPLY WITH |
| 407 AND WITH ASME A17.1 (INCORPORATED BY REFERENCE, SEE |
| ?REFERENCED STANDARDS? IN CHAPTER 1). THEY SHALL BE |
| PASSENGER ELEVATORS AS CLASSIFIED BY ASME A17.1. |
| ELEVATOR OPERATION SHALL BE AUTOMATIC. |
| |
| 13. 1003.7 FBC[B] ELEVATORS, ESCALATORS AND MOVING |
| WALKS. ELEVATORS, ESCALATORS AND MOVING WALKS SHALL NOT |
| BE USED AS A COMPONENT OF A REQUIRED MEANS OF EGRESS |
| FROM ANY OTHER PART OF THE BUILDING. EXCEPTION: |
| ELEVATORS USED AS AN ACCESSIBLE MEANS OF EGRESS IN |
| ACCORDANCE WITH SECTION 1009. |
| |
| 14. 2702.2.2 FBC[B] ELEVATORS AND PLATFORM LIFTS. |
| STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS AND |
| PLATFORM LIFTS AS REQUIRED IN SECTIONS 1009.4, 1009.5, |
| 3003.1, 3007.8 AND 3008.8. |
| IF ELEVATOR IS BEING USED FOR ACCESSIBLE MEANS OF |
| EGRESS, HOW IS BACK-UP POWER BEING SUPPLIED? |
| OTHERWISE, PLEASE PROVIDE ALTERNATIVE ACCESSIBLE PATH |
| OF EGRESS FROM SECOND FLOOR SPACE. |
| |
| 15. 3003.1 FBC[B] STANDBY POWER. IN BUILDINGS AND |
| STRUCTURES WHERE STANDBY POWER IS REQUIRED OR FURNISHED |
| TO OPERATE AN ELEVATOR, THE OPERATION SHALL BE IN |
| ACCORDANCE WITH SECTIONS 3003.1.1 THROUGH 3003.1.4. |
| |
| 16. 407.4.1 FBC[A] CAR DIMENSIONS. INSIDE DIMENSIONS OF |
| ELEVATOR CARS AND CLEAR WIDTH OF ELEVATOR DOORS SHALL |
| COMPLY WITH TABLE 407.4.1. |
| -PLEASE ADD CAB DIMENSIONS AND TURNING SPACE ON PLANS. |
| |
| 17. ASCE 7-10 SECTION 4.5.1 LOADS ON HANDRAIL AND |
| GUARDRAIL SYSTEMS. |
| -PROVIDE ENGINEERING FOR THE RAIL AT PULPIT, OR |
| INDICATE THAT IT WILL BE A DEFERRED SUBMITTAL. |
| |
| 18. 1609.1 FBC[B] APPLICATIONS. BUILDINGS, STRUCTURES |
| AND PARTS THEREOF SHALL BE DESIGNED TO WITHSTAND THE |
| MINIMUM WIND LOADS PRESCRIBED HEREIN. |
| -PLEASE PROVIDE ENGINEERING TO SHOW HOW LEXAN PANELS |
| MEET PRESSURES BASED ON SPAN, EDGE DISTANCE AND GLASS |
| SEPARATION. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -IF ANY SPEC SHEETS OR PRDUCT APPROVALS ARE ADDED, |
| PLEASE UPLOAD THEM AS MULTIPAGE FORMAT PDF IN |
| SUPPORTING DOCUMENTS. |
| -DIGITAL RESUBMITTAL UPON ALL REVIEWS COMPLETED. |
| |