Date |
Text |
2018-12-13 10:05:07 | ****CORRECTIONS**** |
| |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| FBC 107. PLEASE PROVIDE MORE INFORMATION : |
| |
| 1. THE SUBMITTED PLANS SHOW AN INTERIOR ROOM LABELED |
| "GARAGE" IN ADDITION TO THE EXISTING GARAGE AT THE |
| FRONT OF THE HOUSE. PLEASE ADDRESS THIS DISCREPANCY. |
| |
| |
| 2. A SHUTTER PRODUCT APPROVAL WAS SUBMITTED WITHOUT ANY |
| OTHER REQUIRED INFORMATION: |
| |
| A. PROVIDE A SKETCH/LAYOUT SHEET SHOWING THE LOCATION |
| OF ALL SHUTTERS TO BE INSTALLED.THIS LAYOUT SHEET |
| SHOULD INDICATE WINDOW/DOOR OPENINGS NUMBERED TO MATCH |
| WITH THE SCHEDULE FOR INSTALLATION OF OPENING |
| PROTECTIVE DEVICES. |
| |
| |
| B. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION |
| OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL |
| INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL |
| SPREADSHEET): |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS?PAGE=2 |
| |
| C. WHEN COMPLETING THE INSTALLATION SCHEDULE FACTORS |
| APPLY DEPENDING ON SUBSTRATE, EDGE DISTANCE AND |
| FASTENER. FOR FASTENER, IF USING TAPCON, BE SPECIFIC AS |
| TO WHICH TAPCON. |
| |
| |
| D. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC |
| R 310.4; INCLUDE ROOM DESIGNATION. |