Plan Review Notes
Plan Review Notes For Permit 18110341
Permit Number 18110341
Review Stop E
Sequence Number 2
Notes
Date Text
2018-12-24 10:39:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BE SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN.
 PROVIDE CORRECTION. FS 471/481; WPB FBC 107.1, 107.2.1,
 107.3.5.1.2 (PLAN AND RISER NOT SIGNED.)
 2. CORRECTED.
  
 NEW COMMENTS:
  
 3. PLAN SHOWS 4/0 ALUMINUM FEEDING THE TWO 200 AMP
 DISCONNECTS. THIS WIRE IS NOT RATED FOR 200 AMPS AND A
 LOAD CALCULATION WAS NOT PROVIDED STATING THAT THIS
 WIRE WILL HANDLE THE LOAD. EITHER CORRECT WIRE SIZE, OR
 PROVIDE LOAD CALCULATION SHOWING THIS WIRE SIZE CAN
 HANDLE THE LOAD. NEC 220, 240.4, 310.15(B)(16)
 4. PLAN SHOWS 250 KCMIL TRIPLEX FEEDING THE TRAILERS.
 THESE FEEDERS ARE REQUIRED TO HAVE AN EQUIPMENT
 GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC 250.110,
 250.122
 5. PLAN SHOWS A SINGLE PHASE SERVICE, BUT THE TRAILER
 PANELS STATE THERE IS 208 VOLTS. IS THIS SERVICE SINGLE
 PHASE 240 VOLT, OR THREE PHASE 208 VOLT? PROVIDE
 CLARIFICATION AND/OR CORRECTIONS. WPB FBC 107.2.1
 6. PROVIDE SERVICE AREA RECEPTACLE. NEC 210.64
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER