Date |
Text |
2018-12-06 10:02:23 | |
| ****CORRECTIONS**** |
| |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1.PLEASE PROVIDE PRODUCT APPROVALS FOR ROOF TILES AND |
| UNDERLAYMENT/BASE MATERIAL. FBC 107.1 |
| 2.PLEASE PROVIDE MANUFACTURER?S INSTRUCTIONS FOR THE |
| VENTED HOOD AND GAS GRILL SHOWN IN SHEET 1. FBC 107.1 |
| 3.PROVIDE LOCATION WITH ATTACHMENTS DETAILS AND EXHAUST |
| LOCATION(INCLUDING TERMINATION) FOR THE VENTED HOOD. |
| FBCR 1307.1 AND 1307.2 |
| 4.THE STUCCO DETAIL NEEDS ADDITIONAL LAYER OF WATER |
| BARRIER. |
| R703.7.3 WATER-RESISTIVE BARRIERS. |
| WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED |
| IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED |
| SHEATHING, SHALL INCLUDE A WATER-RESISTIVE |
| VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST |
| EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE |
| INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH |
| THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE |
| AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION |
| R703.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE |
| BARRIER IS DIRECTED BETWEEN THE LAYERS. |
| EXCEPTION: WHERE THE WATER-RESISTIVE BARRIER THAT IS |
| APPLIED OVER WOOD-BASED SHEATHING HAS A WATER |
| RESISTANCE EQUAL TO OR GREATER THAN THAT OF 60-MINUTE |
| GRADE D PAPER AND IS SEPARATED FROM THE STUCCO BY AN |
| INTERVENING, SUBSTANTIALLY NONWATER-ABSORBING LAYER OR |
| DESIGNED DRAINAGE SPACE. |
| 5.PLEASE PROVIDE DECK RAFTERS SIZE. FBC 107.2 |
| 6.PLEASE PROVIDE THE SPACING FOR THE #5 FILL CELLS |
| REBAR. FBC 107.2.1 |
| |