Plan Review Notes
Plan Review Notes For Permit 18110093
Permit Number 18110093
Review Stop G
Sequence Number 4
Notes
Date Text
2019-08-14 10:29:444TH REVIEW: 18110093
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS: 8/14/19 PLEASE CONTACT ME WITH ANY
 QUESTIONS
  
 THE RESPONSE LETTER DATED 7/18 DOES NOT MATCH MY
 COMMENTS FROM 6/04 PLEASE ADDRESS THE FOLLOWING
 COMMENTS.
  
  
 1. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT
 2"PSI THE SIZING TABLE SHOWN FBCFG TABLE 402.4(3) IS
 LESS THAN 2PSI PLEASE CLARIFY IF THE SYSTEM IS A 2PSI
 IT WILL REQUIRE PRESSER REGULATORS AT EACH GAS
 APPLIANCES. PER FBC FG 410.2
  
 2. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 SYSTEM PRESSURE SHALL BE SHOWN ON RISER THE PRESSURE ON
 THE GAS UTILITIES SIDE OF THE METER IS NOT REQUIRED
 ONLY THE BUILDING SIDE OF THE METER IS REQUIRED
  
 DUE TO THE LACK OF INFORMATION ON WATER HEATER THE
 FOLLOWING COMMENTS SHALL BE ADDRESSED
  
 3. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR WATER
 HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. WE WILL NEED THESE BEFORE GAS PERMIT IS
 ISSUED. CAN NOT BE DIFFERED SUBMITTAL
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 OR 2017 FBC-RES.
 SEC.G 2407.1 AND G2439.4 IF THE WATER HEATER IS DIRECT
 VENT PROVIDE MANUFACTURE SPECIFICATIONS TO VERIFY.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH,
 SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL
 GAS CODE SEC. 502 THRU 505.
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]