Plan Review Notes For Permit 18110093 |
Permit Number |
18110093 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-06-04 08:56:32 | PLUMBING NOTE: | | | | THE VENT FOR THE BAR AREA THRU THE SIDE WALL SHALL | | COMPLY WITH. | | FBC PL 903.6 EXTENSION THROUGH THE WALL. | | VENT TERMINALS EXTENDING THROUGH THE WALL SHALL | | TERMINATE AT A POINT NOT LESS THAN 10 FEET (3048 MM) | | FROM A LOT LINE AND NOT LESS THAN 10 FEET (3048 MM) | | ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS SHALL NOT | | TERMINATE UNDER THE OVERHANG OF A STRUCTURE WITH SOFFIT | | VENTS. SIDE WALL VENT TERMINALS SHALL BE PROTECTED TO | | PREVENT BIRDS OR RODENTS FROM ENTERING OR BLOCKING THE | | VENT OPENING. | | | | | | A) SEPARATE PERMIT IS REQUIRED FOR BACKFLOW ASSEMBLIES | | PER WPB UTILITIES. | | B) SEPARATE PERMIT IS REQUIRED FOR THE GREASE | | INTERCEPTOR | | C) SEPARATE PERMIT IS REQUIRED FOR GENERATOR AND FUEL | | SYSTEM | | D) SEPARATE PERMIT IS REQUIRED FOR FUEL GAS | | E) KITCHEN IS PERMITTED AS VENILLA SHELL SEPARATE | | PERMIT REQUIRED FOR BUILD OUT OF KITCHEN INCLUDING | | GREASE INTERCEPTOR CALCULATIONS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|