Plan Review Notes
Plan Review Notes For Permit 18110093
Permit Number 18110093
Review Stop M
Sequence Number 3
Notes
Date Text
2019-06-04 10:08:142ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18110093
 6/4/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A0.02, M-101, & M-102: IT APPEARS THAT SMOKE
 DAMPERS MAY BE MISSING FOR DUCTS PENETRATING SMOKE
 PARTITIONS. PLEASE REVISE THE LIFE SAFETY PLANS TO
 CLEARLY SHOW THE LOCATIONS OF ALL SMOKE PARTITIONS, AND
 REVISE THE MECHANICAL PLANS TO SHOW THE SMOKE DAMPER
 LOCATIONS (IF APPLICABLE)- SEE SECTION 607.5.7 FBC M.
  
 2) M-102: THE PLANS ARE STILL NOT CLEARLY INDICATING
 HOW COMBUSTION AIR AND VENTING FOR THE GAS WATER HEATER
 WILL BE ACCOMPLISHED. THERE IS ONE NEW EXTERIOR WALL
 CAP THAT IS NOTED AS WH EXHAUST AIR AND COMBUSTION
 MAKEUP AIR. TYPICALLY DIRECT VENTS TERMINATE AT THE
 EXTERIOR OF THE BUILDING AND DO NOT REQUIRE A WALL CAP.
 IS THIS A CONCENTRIC VENT THAT WEILL BE BRINGING IN THE
 COMBUSTION AIR? IT MAY BE HELPFUL TO PROVIDE A DETAIL
 OR ENLARGED DRAWING. PLEASE NOTE THAT IF COMBUSTION IS
 TO BE BROUGHT IN THOUGH THE OPENING, IT SHALL BE SIZED
 AND LOCATED IN ACCORDANCE WITH SECTION 304.6.2 FBC FG.
  
 3) PLEASE PROVIDE A MASTER LIST ON THE PLAN OF ALL
 REQUESTED DEFERRED SUBMITTALS INCLUDING, BUT NOT
 LIMITED TO:
  
 A) KITCHEN EQUIPMENT PLANS AND SCHEDULES INCLUDING
 PRODUCT DATA SHEETS FOR GAS-FIRED COOKING APPLIANCES.
 B) KITCHEN HOOD AND EXHAUST SYSTEM PLANS
 C) FIRE SUPPRESSION PLAN.
 D) WALK-IN COOLER AND FREEZER PLANS.
 E) GENERATOR
 G) SITE SPECIFIC WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE CHILLER AND ALL OTHER EXTERIOR MECHANICAL
 EQUIPMENT AND COMPONENTS.
 H) FL. PRODUCT APPROVALS AND/OR MIAMI-DADE NOAS FOR THE
 EXHAUST AND O/A LOUVERS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  