2019-06-04 09:47:53 | 3RD REVIEW: 18110093 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| |
| |
| GAS COMMENTS:3RD REQUEST |
| |
| 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| INDICATE TYPE OF PIPE ON THE RISER DIAGRAM. THE BRANCH |
| TO THE GENERATOR IS BURIED UNDERGROUND STEEL PIPE SHALL |
| NOT BE DIRECT BURIAL IT WILL NEED TO BE SLEEVED, |
| PROVIDE A DETAIL SHOWING A SEALED SLEEVE OR RUN PE |
| PIPE. |
| TYPE OF MATERIAL SHALL BE SHOWN ON GAS PIPING ISOMETRIC |
| DRAWING |
| |
| 4. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT |
| 2"PSI THE SIZING TABLE SHOWN FBCFG TABLE 402.4(3) IS |
| LESS THAN 2PSI PLEASE CLARIFY IF THE SYSTEM IS A 2PSI |
| IT WILL REQUIRE PRESSER REGULATORS AT EACH GAS |
| APPLIANCES. PER FBC FG 410.2 |
| |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| SYSTEM PRESSURE SHALL BE SHOWN ON RISER THE PRESSURE ON |
| THE GAS UTILITIES SIDE OF THE METER IS NOT REQUIRED |
| ONLY THE BUILDING SIDE OF THE METER IS REQUIRED |
| |
| |
| 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. WE WILL NEED THESE BEFORE GAS PERMIT IS |
| ISSUED. CAN NOT BE DIFFERED SUBMITTAL |
| |
| 10. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC-FUEL GAS CODE SEC.304.1, 614.6 OR 2017 FBC-RES. |
| SEC.G 2407.1 AND G2439.4 IF THE WATER HEATER IS DIRECT |
| VENT PROVIDE MANUFACTURE SPECIFICATIONS TO VERIFY. |
| |
| NEW COMETS: |
| |
| 1. PLEASE SIZE PIPE TO FUTURE KITCHEN. WPB AMENDMENTS |
| TO FBC SEC.107.2.1 |
| |
| 2. PLACE NOTE ON PLAN SEPARATE PERMIT REQUIRED FOR |
| KITCHEN GAS PIPING. WPB AMENDMENTS TO FBC SEC.107.2.1 |
| |
| 3. THE 3/4 LINE TO THE WATER HEATER IS UNDERSIZED PER |
| TABLE 402.4(3) SHALL BE 1" |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |