2019-06-04 09:47:533RD REVIEW: 18110093
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
  
  
 GAS COMMENTS:3RD REQUEST
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 INDICATE TYPE OF PIPE ON THE RISER DIAGRAM. THE BRANCH
 TO THE GENERATOR IS BURIED UNDERGROUND STEEL PIPE SHALL
 NOT BE DIRECT BURIAL IT WILL NEED TO BE SLEEVED,
 PROVIDE A DETAIL SHOWING A SEALED SLEEVE OR RUN PE
 PIPE.
 TYPE OF MATERIAL SHALL BE SHOWN ON GAS PIPING ISOMETRIC
 DRAWING
  
 4. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT
 2"PSI THE SIZING TABLE SHOWN FBCFG TABLE 402.4(3) IS
 LESS THAN 2PSI PLEASE CLARIFY IF THE SYSTEM IS A 2PSI
 IT WILL REQUIRE PRESSER REGULATORS AT EACH GAS
 APPLIANCES. PER FBC FG 410.2
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 SYSTEM PRESSURE SHALL BE SHOWN ON RISER THE PRESSURE ON
 THE GAS UTILITIES SIDE OF THE METER IS NOT REQUIRED
 ONLY THE BUILDING SIDE OF THE METER IS REQUIRED
  
  
 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. WE WILL NEED THESE BEFORE GAS PERMIT IS
 ISSUED. CAN NOT BE DIFFERED SUBMITTAL
  
 10. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 OR 2017 FBC-RES.
 SEC.G 2407.1 AND G2439.4 IF THE WATER HEATER IS DIRECT
 VENT PROVIDE MANUFACTURE SPECIFICATIONS TO VERIFY.
  
 NEW COMETS:
  
 1. PLEASE SIZE PIPE TO FUTURE KITCHEN. WPB AMENDMENTS
 TO FBC SEC.107.2.1
  
 2. PLACE NOTE ON PLAN SEPARATE PERMIT REQUIRED FOR
 KITCHEN GAS PIPING. WPB AMENDMENTS TO FBC SEC.107.2.1
  
 3. THE 3/4 LINE TO THE WATER HEATER IS UNDERSIZED PER
 TABLE 402.4(3) SHALL BE 1"
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  