Plan Review Notes For Permit 18110093 |
Permit Number |
18110093 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-06-06 14:41:56 | 3RD REVIEW | | ALL OTHER COMMENTS ARE RESOLVED | | | | 15.) REG ? STAIR 110, 210 & 310 IS AN EXIT ACCESS STAIR | | UNDER FBC 1019.3.4 AND VERTICAL OPENINGS ARE ALLOWED | | PER 712.1.12. CLOSELY SPACED SPRINKLER HEADS PER | | 903.3.1.1 (ON A SEPARATE PERMIT) WILL BE INSTALLED AT | | VERTICAL OPENINGS ON 1ST AND 2ND FLOORS AND A SOFFIT IS | | PROVIDED WHICH SERVES AS A DRAFT CURTAIN. ALLOWABLE | | EXIT ACCESS TRAVEL DISTANCE FOR ?A? PER 1017.2 IS 250?. | | TRAVEL DISTANCES PROVIDED TO EXTERIOR EXIT ACCESS DOORS | | ARE EQUAL TO OR LESS THAN 202?. | | | | 15) 1023.1 FBC[BUILDING] STAIR 310 IS USED FOR EGRESS | | AND SHOULD FOLLOW SECTION 1023 FOR INTERIOR STAIR. | | VERTICAL OPENINGS WILL FOLLOW 712.1.9 AND 404 FOR | | ATRIUMS. | | THE REASON THIS COMMENT REMAINS IS THAT, WHILE YOU MEET | | MOST OF THE REQUIREMENTS FOR 712.1.12, OPENINGS PER | | 1019.3 NOTE #1 EXIT ACCESS STAIRWAYS AND RAMPS THAT | | SERVE OR ATMOSPHERICALLY COMMUNICATE BETWEEN ONLY TWO | | STORIES. SUCH INTERCONNECTED STORIES SHALL NOT BE OPEN | | TO OTHER STORIES. | | BECAUSE THAT IS AN EXIT STAIR IT SHOULD BE ENCLOSED OR | | ONLY SERVE 2 FLOORS. | | | | DYLAN BATTLES | | 561-805-6718 | | [email protected] | | | | THE CITY OF WEST PALM BEACH | | BUILDING PLANS EXAMINER PX4191 | | |
|