Plan Review Notes
Plan Review Notes For Permit 18110093
Permit Number 18110093
Review Stop B
Sequence Number 3
Notes
Date Text
2019-06-06 14:41:563RD REVIEW
 ALL OTHER COMMENTS ARE RESOLVED
  
 15.) REG ? STAIR 110, 210 & 310 IS AN EXIT ACCESS STAIR
 UNDER FBC 1019.3.4 AND VERTICAL OPENINGS ARE ALLOWED
 PER 712.1.12. CLOSELY SPACED SPRINKLER HEADS PER
 903.3.1.1 (ON A SEPARATE PERMIT) WILL BE INSTALLED AT
 VERTICAL OPENINGS ON 1ST AND 2ND FLOORS AND A SOFFIT IS
 PROVIDED WHICH SERVES AS A DRAFT CURTAIN. ALLOWABLE
 EXIT ACCESS TRAVEL DISTANCE FOR ?A? PER 1017.2 IS 250?.
 TRAVEL DISTANCES PROVIDED TO EXTERIOR EXIT ACCESS DOORS
 ARE EQUAL TO OR LESS THAN 202?.
  
 15) 1023.1 FBC[BUILDING] STAIR 310 IS USED FOR EGRESS
 AND SHOULD FOLLOW SECTION 1023 FOR INTERIOR STAIR.
 VERTICAL OPENINGS WILL FOLLOW 712.1.9 AND 404 FOR
 ATRIUMS.
 THE REASON THIS COMMENT REMAINS IS THAT, WHILE YOU MEET
 MOST OF THE REQUIREMENTS FOR 712.1.12, OPENINGS PER
 1019.3 NOTE #1 EXIT ACCESS STAIRWAYS AND RAMPS THAT
 SERVE OR ATMOSPHERICALLY COMMUNICATE BETWEEN ONLY TWO
 STORIES. SUCH INTERCONNECTED STORIES SHALL NOT BE OPEN
 TO OTHER STORIES.
 BECAUSE THAT IS AN EXIT STAIR IT SHOULD BE ENCLOSED OR
 ONLY SERVE 2 FLOORS.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  