Plan Review Notes
Plan Review Notes For Permit 18110093
Permit Number 18110093
Review Stop P
Sequence Number 2
Notes
Date Text
2019-04-18 15:26:142ND REVIEW: 18110093
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A4.05, A4.06, A4.07 SHOW THE DIMENSIONS ON THE
 CLEAR FLOOR SPACE 2ND REQUEST SHALL COMPLY WITH FLORIDA
 ACCESSIBILITY 604.3.1, 608.2.1 , 606.2 ADDITIONAL
 INFORMATION REQUIRED ON PLANS PER WPB AMEND TO FBC
 107.2.1
  
 2.SHT A4.07 SHOW HEIGHT OF SHOWER SEAT SHALL COMPLY
 WITH FLORIDA ACCESSIBILITY 610.3 ADDITIONAL INFORMATION
 REQUIRED ON PLANS PER WPB AMEND TO FBC 107.2.1
  
 3.SHT A4.07 SHOW DIMENSION BETWEEN THE FRONT OF THE
 SHOWER AND THE SIDE WALL OF TOILET. PER WPB AMEND TO
 FBC 107.2.1 FLORIDA ACCESSIBILITY 604.3.1 ADDITIONAL
 INFORMATION REQUIRED ON PLANS PER WPB AMEND TO FBC
 107.2.1
  
 4. PLACE NOTE ON PLAN ALL VENTS SHALL COMPLY WITH. FBC
 PL TABLE 906.1 906.2 ADDITIONAL INFORMATION REQUIRED ON
 PLANS PER WPB AMEND TO FBC 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]