Plan Review Notes For Permit 18110093 |
Permit Number |
18110093 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-04-18 15:26:14 | 2ND REVIEW: 18110093 | | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. SHT. A4.05, A4.06, A4.07 SHOW THE DIMENSIONS ON THE | | CLEAR FLOOR SPACE 2ND REQUEST SHALL COMPLY WITH FLORIDA | | ACCESSIBILITY 604.3.1, 608.2.1 , 606.2 ADDITIONAL | | INFORMATION REQUIRED ON PLANS PER WPB AMEND TO FBC | | 107.2.1 | | | | 2.SHT A4.07 SHOW HEIGHT OF SHOWER SEAT SHALL COMPLY | | WITH FLORIDA ACCESSIBILITY 610.3 ADDITIONAL INFORMATION | | REQUIRED ON PLANS PER WPB AMEND TO FBC 107.2.1 | | | | 3.SHT A4.07 SHOW DIMENSION BETWEEN THE FRONT OF THE | | SHOWER AND THE SIDE WALL OF TOILET. PER WPB AMEND TO | | FBC 107.2.1 FLORIDA ACCESSIBILITY 604.3.1 ADDITIONAL | | INFORMATION REQUIRED ON PLANS PER WPB AMEND TO FBC | | 107.2.1 | | | | 4. PLACE NOTE ON PLAN ALL VENTS SHALL COMPLY WITH. FBC | | PL TABLE 906.1 906.2 ADDITIONAL INFORMATION REQUIRED ON | | PLANS PER WPB AMEND TO FBC 107.2.1 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|