2019-04-24 09:28:37 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #18110093 |
| 4/24/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) IN ACCORDANCE WITH THE ARCHITECT'S NARRATIVE, THE |
| KITCHEN COOKING APPLIANCES AND EQUIPMENT, THE KITCHEN |
| HOODS AND FIRE SUPPRESSION SYSTEMS WILL BE DONE UNDER |
| SEPARATE PERMIT. AS A RESULT, THE NARRATIVE INDICATES |
| GAS-FIRED COOKING APPLIANCE SUBMOTTALS, COMBUSTION AIR |
| CALCULATIONS, AIR BALANCE CALCULATIONS, AND MAKE UP AIR |
| TEMPERATURE COMPLIANCE WILL ALSO BE DEFERRED TO A |
| FUTURE DATE. PLEASE PLACE LARGE BOLD NOTES ON THE PLAN |
| TO INDICATE THIS FOR PUBIC RECORD AND FOR THE |
| CONTRACTORS IN THE FIELD. |
| |
| 2) CLARIFY IF THE GENERATOR IS TO BE UNDER SEPARATE |
| PERMIT. IF SO, PLEASE ADD IT TO THE LIST OF DEFERRED |
| SUBMITTALS LISTED IN COMMENT #1. OTHERWISE, COMPLY WITH |
| ITEMS A-F LISTED BELOW: |
| |
| A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| GENERATOR, FUEL PIPING, ENGINE EXHAUST PIPE, MUFFLER, |
| AND ALL OTHER ASSOCIATED SYSTEM COMPONENTS- SECTION |
| 304.1 FBC M. |
| |
| B) SUBMIT THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE |
| GENERATOR- SECTION 915.1 FBC M. THE MANUFACTURER'S |
| SPECIFICATIONS AND/OR UL CERTIFICATE SHALL INDICATE THE |
| GENERATOR IS IN COMPLIANCE WITH NFPA 37. |
| |
| C) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FUEL |
| TANK THAT INCLUDES THE TANK'S UL LISTING- UL 142 OR UL |
| 2085- SEE SECTION 21.4.2.1.1 NFPA 30. |
| |
| D) PROVIDE AN EXHAUST PIPE DIAGRAM SHOWING THE TOTAL |
| SYSTEM RUN AND LENGTH MEASUREMENT, AND TERMINATION |
| LOCATION, AND CLEARANCE DISTANCES GRAVITY OR MECHANICAL |
| AIR INTAKES INTO THE BUILDING PLEASE INCLUDE ALL |
| COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER.- SEE |
| SECTION 8.1- 8.4 NFPA 37, AND SECTION 501.3.1 FBC M. |
| |
| E) PROVIDE DETAILS AND SPECIFICATIONS FOR NORMAL AND |
| EMERGENCY RELIEF VENTING OF THE TANK, INCLUDING VENT |
| PIPING RUNS AND TERMINATION LOCATIONS- SECTION 24.13 |
| NFPA 30. |
| |
| F) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE |
| GENERATOR TO THE STRUCTURAL SLAB- SECTION 301.15 FBC M. |
| |
| 3) SHEET M-102: AS PREVIOUSLY NOTED IN THE 1ST REVIEW, |
| THE SUPPLY DUCT AND DIFFUSER ARE PROHIBITED FROM |
| PENETRATING INTO THE INTERIOR EXIT STAIRWAY- SECTIONS |
| 1023.5 & 1023.6 FBC B. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |