2019-04-19 08:19:142ND REVIEW: 18110093
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
  
  
 GAS COMMENTS:2ND REQUEST
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 INDICATE TYPE OF PIPE ON THE RISER DIAGRAM. THE BRANCH
 TO THE GENERATOR IS BURIED UNDERGROUND STEEL PIPE SHALL
 NOT BE DIRECT BURIAL IT WILL NEED TO BE SLEEVED,
 PROVIDE A DETAIL SHOWING A SEALED SLEEVE OR RUN PE
 PIPE.
  
 4. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT
 2"WG AND PRESSURE DROP OF 3"WG IT GIVES A TABLE WHICH
 IS LESS THAN 2 PSI AND PRESSURE DROP OF 6"WC PLEASE
 CLARIFY. WPB AMENDMENTS TO FBC SEC.107.2.1. WHAT DOES
 WG STAND FOR IS IT WATER COLUMN IF THATS THE CASE 2"WC
 IS VERY LOW I'LL NEED TO SEE THE MANUFACTURE SPEC TO
 VERIFY THAT IS SUFFICIENT.
  
  
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 SHOW ON RISER
  
  
 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. WE WILL NEED THESE BEFORE GAS PERMIT IS
 ISSUED.
  
 10.FIRST SECTION OF PIPE AFTER METER IS UNDER SIZED IT
 SHOULD BE 11/4" TO MATCH PIPING UPSTREAM. PER FBC FG
 TABLE 402.3(3) WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 11. SHT. P-902 KEY NOTE #4 WHAT IS AN ACCEPTANCE TANK
 PLEASE CLARIFY. WPB AMENDMENTS TO FBC SEC.107.2.1.
 PLEASE CHANGE PLAN TO THERMAL EXPANSION TANK SO THAT
 THE FIELD INSPECTOR CAN VERIFY COMPLIANCE.
  
 NEW COMMENT
  
 1. THE VALVE FOR FUTURE PIPING SHALL BE LOCKOUT TYPE
 PLEASE PROVIDE A DETAIL OR NOTE THAT THE FUTURE PIPING
 SHALL BE CAPPED AND HAVE A LOCK OUT VALVE.PER WPB
 AMENDMENTS TO FBC SEC.107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711