Plan Review Notes
Plan Review Notes For Permit 18110093
Permit Number 18110093
Review Stop B
Sequence Number 2
Notes
Date Text
2019-05-03 11:19:58 
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18110093
 ADD: 609 8TH ST.
 CONT: COOPER CONSTRUCTION MANAGEMENT & CONSULTING
 TEL: 561-588-5222
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. JAN. 22/ 2019
 ACTION: DENIED
  
 1) OK
  
 2) OK - IN PROGRESS
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  -THE INTENT OF THE COMMENT WAS TO CONVEY THAT IT IS
 ADVANTAGOUS TO UTILIZE ONE FIRE STOPPING CONTRACTOR OR
 MAKE SURE EACH TRADE IS USING THE FIRESTOPPING TYPES.
  
 3) OK.
 -NEW COMMENT: SHEET S0.1 UNDER FOUNDATIONS SECTION B(3)
 STATES SHALLOW FOUNDATIONS AT LEAST 12 INCHES BELOW
 GRADE, BUT THE SOILS REPORTS IS CALLING FOR SHALLOW
 FOUNDATIONS MINIMUM 18 INCHES BELOW. PLEASE COORDINATE
 THE PLANS WITH THE REPORT.
  
 4A) OK. VERIFTY THAT THIS IS NOT EXPOSURE C WITH M.R.H.
 OVER 30 FEET AND B TERRAIN EXTENDING 2600 FEET FROM THE
 SITE.
  
 4B) OK
  
 4C) OK
  
 5) OK- THE FOLLOWING WILL BECOME PROVISOS (NO RESPONSE
 REQUIRED)
 (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
 (H) HANDRAILS AND GUARDS
 (I) STAGE CURTAINS
  
 5A) OK
  
 5B) OK
  
 6) OK. PROVIDE COPY OF RECORDED UNITY OF TITLE PRIOR TO
 PERMIT ISSUANCE.
  
 7A) OK
  
 7B) OK
  
 7C) OK
  
 7D) THIS WILL TRIPLE THE OCCUPANT LOAD PLEASE PROVIDE A
 NEW ANALYSIS FOR THIS FLOOR FOR EXITING. PLEASE SHOW
 HOW THE OCCUPANTS WILL EXIT SHOW THE EXITING FOR THIS
 FLOOR AND THE ADDITIONAL LOAD FROM THE MEZZANINE. THE
 MEZZANINE OCCUPANT LOAD IS FIGURED IN WITH THE 2ND
 FLOOR OCCUPANT LOAD FOR EXITING. PLEASE PROVIDE THE
 TOTAL OCCUPANT LOAD FOR THE 2ND FLOOR WITH MEZZANINE
 OCCUPANT LOAD. FBC-B 1019.1. 2017 FBC-B 505.2.2 MEANS
 OF EGRESS. THE MEANS OF EGRESS FOR MEZZANINES SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF CHAPTER 10.
 -COMMENT NOT ADDRESSED-SHEET A0.02 BALCONY LEVEL NOW
 STATES 570 OCCUPANTS BELOW, BUT 2 ND FLOOR DOES NOT
 ACCOUNT FOR THE ADDITIONAL NUMBER AT THE 2 ND FLOOR
 EXITS.
  
 7E) OK
  
 7F) OK
  
 7G) OK
  
 7H) OK
  
 7I) OK
  
 7I) OK
  
 7J) OK
  
 7K) OK
  
 7L) OK
  
 8) OK
  
 8B) OK
  
 8C) OK
  
 8C) OK
  
 9) OK
  
 9A) OK
  
 9B) OK
  
 10) OK
  
 11) OK
  
 12) OK
  
 2ND REVIEW 5/3/2019
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 NEW COMMENTS:
 13) 107.3.5 FBC[AMENDED] MEZZANINE/BALCONY LEVEL SHOWS
 RAMS DOWN IN HALLWAY TO GET TO STAGE ELEVATION AND
 SECTIONS ON A3.03 SHOW A 6 INCH STEP FROM HALL MO2 TO
 LOBBY 311.
 -PLEASE SHOW THIS STEP IN PLAN VIEW.
  
 14) 107.3.5 FBC[AMENDED] SHEET A1.03 SHOWS DOOR CALL
 OUT 316 OUTSIDE OF STAIR 326. PLAN DOES NOT SHOW THE
 DOOR SWING, BUT DOOR SCHEDULE DOES HAVE DOOR THERE.
  A) PLEASE REVIEW WHAT IS HERE AND REVISE.
  B) ALSO, LOOK AT DOUBLE DOORS LABLED 130 AND 135 IN
 HALL M02. I DO NOT SEE THESE DOORS ON DOOR SCHEDULE.
  C) DOOR 311 TO ROOF GARDEN. SECTION 1/A3.01 LOOKS LIKE
 DOOR IS AT SAME ELEVATION AS ROOF AND INTERIOR. SECTION
 1/A3.03 LOOKS LIKE THE DOOR MAY BE RAISED. PLEASE
 VERIFY HOW ACCESSIBLE PATH WORKS FROM ELEVATOR P1 TO
 ROOF GARDEN. ALSO, DOES ELEV F1 HAVE A STEP DOWN AT
 MEZZANINE/PATIO LEVEL?
  
 15) 1023.1 FBC[BUILDING] STAIR 310 IS USED FOR EGRESS
 AND SHOULD FOLLOW SECTION 1023 FOR INTERIOR STAIR.
 VERTICAL OPENINGS WILL FOLLOW 712.1.9 AND 404 FOR
 ATRIUMS.
  
 16) 1029.9.1 MINIMUM AISLE WIDTH.
  -COODINATE LIFE SAFETY PLAN WITH FLOOR PLAN TO SHOW
 EXIT ACCESS AISLES. FLOOR PLAN SHOWS TABLES THAT WOULD
 BE IN THE ACCESS AILES SHOWN ON LIFE SAFETY. ALSO,
 REVIEW SECTION 1029.12.1 FOR SEATING AT TABLES NEXT TO
 AISLES.
  
 17) 456.3.2.2 PUBLIC BATHROOMS SHALL BE COMPLETELY
 ENCLOSED AND SHALL HAVE TIGHT-FITTING, SELF-CLOSING
 DOORS OR, IN PUBLIC LODGING ESTABLISHMENTS OR BATHROOMS
 LOCATED OUTSIDE A PUBLIC FOOD SERVICE, HAVE ENTRANCES
 AND EXITS CONSTRUCTED IN SUCH A MANNER AS TO ENSURE
 PRIVACY OF OCCUPANTS.
  -UPDATE DOOR HARDWARE SCHEDULE FOR CLOSERS.
  
 18) 1010.1.10 PANIC AND FIRE EXIT HARDWARE.
  -REVIEW WHICH DOORS REQUIRE EXIT HARDWARE AND ADD TO
 DOOR SCHEDULE.
  
  
  
  
  
  
  
  
  
  