2019-01-18 10:30:10 
 1ST REVIEW: 18110093
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BATHROOM OPENING INTO THE KITCHEN PREP AREA IS A
 CODE VIOLATION. TOILET ROOMS SHALL NOT OPEN DIRECTLY
 INTO A ROOM USED FOR THE PREPARATION OF FOOD FOR
 SERVICE TO THE PUBLIC. PER FBC PL 403.3.2
  
 2. IN THE MULTI USER BATHROOMS AT LEAST ONE LAVATORY
 SHALL COMPLY WITH 606 AND SHALL NOT BE LOCATED IN A
 TOILET COMPARTMENT. PER FBC ACC 213.3.4
  
 3. SHT A4.07 DETAIL 1 THE 36" INSIDE DIMENSION FOR THE
 TRANSFER SHOWER IS NOT A MINIMUM IT SHALL BE AN EXACT
 36" CLEAR INSIDE DIMENSION. PER FBC ACC 608.2.1
  
 4. PROVIDE A LEGEND FOR THE CLEAR FLOOR SPACE AROUND
 THE ACCESSIBLE FIXTURES OR SHOW DIMENSIONS ON EACH
 SPACE. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. A4.07 DETAIL ONE SHOW A 60X56" CLEAR FLOOR
 SPACE FOR THE TOILET AND A 36"X48" IN FRONT OF THE
 SHOWER WITH 1 END LINED UP WITH CONTROL WALL. PER FBC
 ACC 604.3.1, 608.2.1
  
 6. SHT. A4.07 DETAIL B IS SHOWING A 2'-6" MIN DIMENSION
 FOR THE SHOWER IT SHALL BE 36". PER FBC ACC 608.2.1
  
 7. SHOW COMPLIANCE WITH FBC ACC 610.3 IN TRANSFER-TYPE
 SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A
 POINT WITHIN 3 INCHES OF THE COMPARTMENT ENTRY. THE TOP
 OF THE SEAT SHALL BE 17 INCHES MINIMUM AND 19 INCHES
 MAXIMUM ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL
 COMPLY WITH 610.3.1 OR 610.3.2.
  
 8. SHT. P-105 IT APPEARS THE WATER PIPING RUNNING UNDER
 THE SLAB TO THE BAR IS MISSED LABELED THE KEY NOTE
 STATES IT AT #4 THE PIPING SHOWS #3 PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 9. PROVIDE FIRE STOPPING DETAILS FOR PLASTIC PIPING.
 PER WPB AMEND TO FBC 107.2.1
  
 10. SHT.P-901 PLEASE REMOVE GAS PING FROM WATER
 ISOMETRIC IT IS TO CONGESTED. PER WPB AMEND TO FBC
 107.2.1
  
 11. SHT P-901 PLEASE SHOW THE FOLLOWING ON THE
 ISOMETRIC THE FLOOR LEVELS, VALVES ON THE DROPS AND
 BRANCHES AND LABEL THE FIXTURES. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 12. SHT P-906 IN ADDING UP ALL THE SQFT I CAME OUT WITH
 2554 WHICH MAKES THE HORIZONTAL PIPING UNDER SIZED 6"
 SHOULD RUN TO THE 4TH BRANCH FROM THE END PLEASE SHOE
 SQFT TABLES ON THE PIPING AND INDICATE WHAT SLOPE THE
 PIPING WILL BE INSTALLED. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 13. THE SANITARY SYSTEM SERVING THE BAR SHALL HAVE A
 MINIMUM OF 1 VENT EXTENDING TO THE OUTDOORS. PER FBC PL
 904.1, 904.1.1
  
 14. SHT. P-904 KEY NOTE #4 LIST A 3" VENT THE VENT FOR
 THE GREASE SYSTEM IS TAGGED #4 BUT IS SIZED AS 2"
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 15. SHT. P-904 THE VENT SHOWN BY ITSELF NEXT TO THE 2ND
 + 3RD FLOOR BATHROOM ISOMETRIC IS TAGGED AS #6 IT IS
 SIZED AT 2" THE KEY NOTE #6 LIST IT AT 3" PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 16. ALL VENTS SHALL COMPLY WITH FBC PL TABLE 906.1,
 906.2
  
 17. SHT. P-904 ON THE ISOMETRIC FOR THE GREASE WASTE
 SYSTEM THE FLOOR SINK APPEARS TO BE MISLABELED AS THE
 FLOOR DRAIN AND THE FLOOR DRAIN IS NOT LABELED PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 18. SHT. P-904 PLEASE SHOE P-TRAP ON ALL FLOOR DRAINS
 AND INDICATE TRAP PRIMER. PER FBC PL 1002.1, 1002.4.1
  
 19. SHT. P-902 PLEASE SHOW SHUT OFF VALVES ON THE DROPS
 AND BRANCHES. PER FBC PL 606.1
  
 20. SHT. P-902 INDICATE ON THE ISOMETRIC A TEMPERATURE
 LIMITING DEVISE COMPLYING WITH ASSE 1070 IS REQUIRED ON
 THE LAVATORY'S IN THE BATHROOMS. PER FBC PL 416.5
  
 21. SHT. A-4.07 GRAB BARS SHALL BE MEASURED TO THE TOP
 OF THE GRIPPING SURFACE FROM FINISHED FLOOR PER FBC ACC
 609.4
  
 22. SHT. P-902 LABEL UNDERGROUND PIPING ON WATER AND
 GAS. PER WPB AMEND TO FBC 107.2.1
  
 23. PROVIDE GREASE INTERCEPTOR SIZING CALCULATIONS. PER
 FBC PL 1003.2
  
 24. THE MOP SINK IN THE KITCHEN AREA SHALL BE INCLUDED
 ON THE GREASE PIPING AND SIZING CALCULATIONS. PER FBC
 PL 1003.3.1
  
 25. PROVIDE PIPING DETAIL FOR GREASE INTERCEPTOR. PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]