Date |
Text |
2019-01-09 08:16:56 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18110093 |
| 1/9/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN |
| EXHAUST HOOD AND FIRE SUPRESSION HOWEVER AN AIR BALANCE |
| CALCULATION MUST BE PROVIDED ON THE MAIN SET OF PLANS- |
| SECTION 508.1.2 FBC M. PLEASE NOTE THAT THE HOOD PLANS |
| SHALL ALSO BE IN COMPLIANCE WITH SECTION 508.1.1 MAKEUP |
| AIR TEMPERATURE. |
| |
| 2) SHEET M-101: SHOW THE LOCATION OF THE KITCHEN |
| EXHAUST HOOD, EXHAUST DUCT, AND EXHAUST DUCT |
| TERMINATION LOCATION- SECTION 107.2.1 WPB. |
| |
| 3) SHEET M-101: THE O/A INTAKES FOR FC-1-3 AND THE HOOD |
| MAKEUP AIR APPEAR TO BE LIOCATED WITHIN 10' OF THE |
| GENERATOR RADIATOR EXHAUST-. PLEASE SHOW THE REQUIRED |
| CLEARANCE DISTANCE MEASUREMENTS ON THE PLAN- SECTION |
| 401.4 FBC M. |
| |
| 4) M-101, M-102: VERIFY ALL O/A INTAKES SHOWN ON THE1ST |
| AND 2ND FLOORS ARE MEETING THE MINIMUM 10' CLEARANCES |
| TO EXHAUST OUTLETS AND DRIVE AND PARKING LOT AREAS PER |
| SECTION 401.4 FBC M. |
| |
| 5) M-102: VERIFY THE RA INLET IN MECH RM 222 IS LOCATED |
| A MINIMUM 10' CLEAR OF ANY DRAFT HOOD APPLIANCES. |
| |
| 6) M-102, A0.02: CLARIFY WHY FIRE DAMPERS ARE SHOWN FOR |
| DUCTS PENETRATING MECH RM 222 AND THE CORRIDOR WALLS. |
| THE LIFE SAFETY PLAN DOES NOT SHOW FIRE-RATED WALLS IN |
| THOSE LOCATIONS. |
| |
| 7) M-102 & M-103: THE SUPPLY DUCTS ARE PROHIBITED FROM |
| PENETRATING AND SUPPLYING AIR TO THE INTERIOR EXIT |
| STAIRWAY- SECTIONS 1023.5 & 1023.6 FBC B. |
| |
| 8) PROVIDE AN ENLARGED KITCHEN EQUIPMENT PLAN AND |
| EQUIPMENT SCHEDULE. A) SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR GAS-FIRED COOKING APPLIANCES- |
| SECTION 107.2.1 WPB. B) INDICATE HOW COMBUSTION AIR IS |
| BEING PROVIDED AND PROVIDE A CALCULATION- SECTION 304 |
| FBC FG. |
| |
| 9) PROVIDE A MECHANICAL ROOF PLAN- SECTION 107.2.1 WPB. |
| |
| 10) GAS WATER HEATER: A) PROVIDE AN EQUIPMENT SCHEDULE |
| AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 624.1 |
| FBC FG. B) PROVIDE VENTING AND COMBUSTION AIR PLANS- |
| SECTIONS 304 AND 503 FBC FG. |
| |
| 11) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| THE CHILLER, GENERATOR, AND ALL OTHER EXTERIOR |
| MECHANICAL EQUIPMENT- SECTION 301.15 FBC M. |
| |
| 12) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE CHILLER |
| AND THE FAN COIL UNITS- SECTION 307.2.1 FBC M. |
| |
| 13) SUBMIT MANUFACTURER'S SPECIFICATIONS AND A FL. |
| PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE LOUVERS- |
| SECTION 401.5 FBC M AND RULE 9N-3 FAC. |
| |
| 14) SHOW THE LOCATION OF THE LEVATOR CONTROL ROOM AND |
| PROVIDE AN INDEPENDENT VENTILATION OR AIR CONDITIONING |
| SYSTEM PER SECTION 3005.2 FBC B. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |