Plan Review Notes
Plan Review Notes For Permit 18110093
Permit Number 18110093
Review Stop M
Sequence Number 1
Notes
Date Text
2019-01-09 08:16:561ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110093
 1/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 EXHAUST HOOD AND FIRE SUPRESSION HOWEVER AN AIR BALANCE
 CALCULATION MUST BE PROVIDED ON THE MAIN SET OF PLANS-
 SECTION 508.1.2 FBC M. PLEASE NOTE THAT THE HOOD PLANS
 SHALL ALSO BE IN COMPLIANCE WITH SECTION 508.1.1 MAKEUP
 AIR TEMPERATURE.
  
 2) SHEET M-101: SHOW THE LOCATION OF THE KITCHEN
 EXHAUST HOOD, EXHAUST DUCT, AND EXHAUST DUCT
 TERMINATION LOCATION- SECTION 107.2.1 WPB.
  
 3) SHEET M-101: THE O/A INTAKES FOR FC-1-3 AND THE HOOD
 MAKEUP AIR APPEAR TO BE LIOCATED WITHIN 10' OF THE
 GENERATOR RADIATOR EXHAUST-. PLEASE SHOW THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS ON THE PLAN- SECTION
 401.4 FBC M.
  
 4) M-101, M-102: VERIFY ALL O/A INTAKES SHOWN ON THE1ST
 AND 2ND FLOORS ARE MEETING THE MINIMUM 10' CLEARANCES
 TO EXHAUST OUTLETS AND DRIVE AND PARKING LOT AREAS PER
 SECTION 401.4 FBC M.
  
 5) M-102: VERIFY THE RA INLET IN MECH RM 222 IS LOCATED
 A MINIMUM 10' CLEAR OF ANY DRAFT HOOD APPLIANCES.
  
 6) M-102, A0.02: CLARIFY WHY FIRE DAMPERS ARE SHOWN FOR
 DUCTS PENETRATING MECH RM 222 AND THE CORRIDOR WALLS.
 THE LIFE SAFETY PLAN DOES NOT SHOW FIRE-RATED WALLS IN
 THOSE LOCATIONS.
  
 7) M-102 & M-103: THE SUPPLY DUCTS ARE PROHIBITED FROM
 PENETRATING AND SUPPLYING AIR TO THE INTERIOR EXIT
 STAIRWAY- SECTIONS 1023.5 & 1023.6 FBC B.
  
 8) PROVIDE AN ENLARGED KITCHEN EQUIPMENT PLAN AND
 EQUIPMENT SCHEDULE. A) SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR GAS-FIRED COOKING APPLIANCES-
 SECTION 107.2.1 WPB. B) INDICATE HOW COMBUSTION AIR IS
 BEING PROVIDED AND PROVIDE A CALCULATION- SECTION 304
 FBC FG.
  
 9) PROVIDE A MECHANICAL ROOF PLAN- SECTION 107.2.1 WPB.
  
 10) GAS WATER HEATER: A) PROVIDE AN EQUIPMENT SCHEDULE
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 624.1
 FBC FG. B) PROVIDE VENTING AND COMBUSTION AIR PLANS-
 SECTIONS 304 AND 503 FBC FG.
  
 11) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE CHILLER, GENERATOR, AND ALL OTHER EXTERIOR
 MECHANICAL EQUIPMENT- SECTION 301.15 FBC M.
  
 12) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE CHILLER
 AND THE FAN COIL UNITS- SECTION 307.2.1 FBC M.
  
 13) SUBMIT MANUFACTURER'S SPECIFICATIONS AND A FL.
 PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE LOUVERS-
 SECTION 401.5 FBC M AND RULE 9N-3 FAC.
  
 14) SHOW THE LOCATION OF THE LEVATOR CONTROL ROOM AND
 PROVIDE AN INDEPENDENT VENTILATION OR AIR CONDITIONING
 SYSTEM PER SECTION 3005.2 FBC B.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  