Date |
Text |
2019-01-18 12:07:49 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| GAS COMMENTS: |
| |
| 1. LABEL METER ON THE RISER IT LOOKS LIKE A RPZ BACK |
| FLOW. PER WPB AMEND TO FBC 107.2.1 |
| |
| 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 3. ON THE GAS INFORMATION BOX IT SHOWS NATURAL GAS BUT |
| GIVES PROPANE TOTAL BTU LOAD. PLEASE CLARIFY. WPB |
| AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 4. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT |
| 2"WG AND PRESSURE DROP OF 3"WG IT GIVES A TABLE WHICH |
| IS LESS THAN 2 PSI AND PRESSURE DROP OF 6"WC PLEASE |
| CLARIFY. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 5. THE BRANCH WITH 1020 BTU IS UNDERSIZED SHOULD BY 1" |
| PER FBC FG TABLE 402.4(4) |
| |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| |
| 8. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF |
| VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE |
| THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER |
| 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES. |
| SEC.G2426 THROUGH G2439. |
| |
| 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. |
| |
| 10. PLEASE SIZE FIRST SECTION OF PIPE AFTER METER. WPB |
| AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 11. SHT. P-902 KEY NOTE #4 WHAT IS AN ACCEPTANCE TANK |
| PLEASE CLARIFY. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE |
| BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. |
| SECS. 10.4, 10.5 OF NFPA 96-08. |
| |
| 13. SUBMIT MANUFACTURER?S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. |
| REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON |
| THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING |
| INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR |
| CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 |
| FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. |
| |
| 14. SHOW PIPING FOR KITCHEN APPLIANCES. WPB AMENDMENTS |
| TO FBC SEC.107.2.1. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |