Plan Review Notes
Plan Review Notes For Permit 18110093
Permit Number 18110093
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-01-07 10:53:29PERMIT #
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) SHEET A0.03: UPDATE THE CODE LIST TO REFERENCE THE
 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2015 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 2) PER NFPA 101: CHAPTERS 12 & 13 (NEW AND EXISTING
 ASSEMBLY OCCUPANCIES) - ASSEMBLY OCCUPANCIES WITH
 OCCUPANT LOADS OF MORE THAN 300...SHALL BE PROVIDED
 WITH AN APPROVED FIRE ALARM SYSTEM.
  
 3) NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL."
  
 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  