2019-01-22 08:46:062017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18110093
 ADD: 609 8TH ST.
 CONT: COOPER CONSTRUCTION MANAGEMENT & CONSULTING
 TEL: 561-588-5222
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. JAN. 22/ 2019
 ACTION: DENIED
  
 1) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S.
 THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 2) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING / FL
 S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) COMPLETED. 109.3.6.1 THRESHOLD INSPECTION PLAN. THE
 ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 FORMS SENT TO: [email protected] MON. JAN. 14/ 2019
 12:54 PM
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) THE STRUCTURAL SHEET S0.1 UNDER THE HEADING
 EARTHWORK & FOUNDATIONS NOTE A INDICATES THAT THE
 FOUNDATION DESIGN WAS BASED ON THE GEOTECHNICAL
 ENGINEERING REPORT PREPARED BY TERRACON CONSULTANTS,
 INC. (REPORT NO. 185072). DATED JULY 20/2018. PLEASE
 SUBMIT AN ELECTRONIC REPORT WITH ELECTRONIC SIGNATURE
 OR A PAPER REPORT WITH SIGNATURE AND SEAL.
  
 4A) THE SHEET S0.1 GENERAL NOTES, DESIGN CRITERIA (4)
 WIND LOADS OR THE WIND DESIGN CRITERIA IS MISSING THE
 MEAN ROOF HEIGHT FOR MULTIPLIERS FOR THE HEIGHT OF THE
 BUILDING AND EXPOSURE. WIND EXPOSURE. APPLICABLE WIND
 DIRECTION IF MORE THAN ONE WIND EXPOSURE IS UTILIZED.
 TABLE 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE
 30.3.1. THE CODE ANALYSIS ON SHEET A0.03 DOES STATE THE
 MAXIMUM BUILDING HEIGHT OF 41 FEET 7 INCHES. THIS IS
 NOT GIVEN IN THE WIND DESIGN CRITERIA, AND THE FACTOR
 FOR HEIGHT AND EXPOSURE IS NOT GIVEN, B EXPOSURE @ 40
 FEET. MULTIPLIER OF 1.09 USED.
  
 4B) THE OTHER ISSUE IS IN NOTE 5 ON SHEET S0.4. DESIGN
 VALUES SHOWN IN THIS TABLE ARE ULTIMATE VALUES FOR USE
 WITH LRFD (LOAD RESISTANCE FACTORED DESIGN). THE 2017
 FBC-B USES PRESSURES FOR COMPONENTS AND CLADDING IN
 VULT( ULTIMATE DESIGN WIND SPEED) AND VASD (ALLOWABLE
 OR NOMINAL SERVICE LOADS). THE SAME HOLDS TRUE IN ASCE
 7-10 CHAPTER 30 HOLDS TRUE TO THE USAGE OF THE
 TERMINOLOGY OF VULT AND VASD. THE TERMINOLOGY OF LRFD
 LENDS ITSELF TO MORE LIKE CONCRETE, STEEL AND TIMBER.
  
 4C) PLEASE SUBMIT THE WIND PRESSURES IN VASD SINCE ALL
 PRODUCT APPROVALS ARE PUBLISHED IN VASD, THE INSPECTORS
 DO NOT HAVE THE TIME TO COMPUTE THE VULT TO VASD. FBC-B
 1609.3.1.
  
 5) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 5A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 5B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6) SHEET C6.1& C2.1 SHOWS THE EXISTING BUILDING GOING
 THROUGH THE PROPERTY LINE FOR LOT 4 & 5, AND THE
 PROPOSED 3 STORY ADDITION GOING THROUGH THE PROPERTY
 LINE BETWEEN LOTS 5 & 6. PLEASE PROVIDE IS THE3 LOTS
 GOING TO BE REPLATED. SO NO PROPERTY LINES GO THROUGH
 THE BUILDING AND THE REQUIREMENT FOR 4 HOUR FIRE WALLS
 WILL NOT BE REQUIRED. 2017 FBC-B TABLE 602 & FIRE WALLS
 FBC-B 706.1.1.
  
 7A) SHEET 005-A0.03 CODE ANALYSIS. THE 2017 FLORIDA
 EXISTING BUILDING CODE, PRESCRIPTIVE COMPLIANCE METHOD.
 CHANGE OF OCCUPANCY. 407.1. 407.1 CONFORMANCE. NO
 CHANGE SHALL BE MADE IN THE USE OR OCCUPANCY OF ANY
 BUILDING UNLESS SUCH BUILDING IS MADE TO COMPLY WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING
 FOR THE USE OR OCCUPANCY. CHANGES IN USE OR OCCUPANCY
 IN A BUILDING OR PORTION THEREOF SHALL BE SUCH THAT THE
 EXISTING BUILDING IS NO LESS COMPLYING WITH THE
 PROVISIONS OF THIS CODE THAN THE EXISTING BUILDING OR
 STRUCTURE WAS PRIOR TO THE CHANGE. SUBJECT TO THE
 APPROVAL OF THE BUILDING OFFICIAL, THE USE OR OCCUPANCY
 OF EXISTING BUILDINGS SHALL BE PERMITTED TO BE CHANGED
 AND THE BUILDING IS ALLOWED TO BE OCCUPIED FOR PURPOSES
 IN OTHER GROUPS WITHOUT CONFORMING TO ALL OF THE
 REQUIREMENTS OF THIS CODE FOR THOSE GROUPS, PROVIDED
 THE NEW OR PROPOSED USE IS LESS HAZARDOUS, BASED ON
 LIFE AND FIRE RISK, THAN THE EXISTING USE.
 PLEASE NOTE THE CODE RESEARCH FOUND ON SHEET A0.03 DOES
 INDICATE THAT THERE WERE 2 FLOORS WITH AN R-2
 OCCUPANCY. SO THERE IS A PARTIAL CHANGE OF OCCUPANCY.
 THE NEW OCCUPANCY (ASSEMBLY) IS A MORE STRINGENT USE
 AND OCCUPANCY THAN THE R2.
  
 2017 FBC-EXISTING BUILDING CODE 401.3 DANGEROUS
 CONDITIONS. THE BUILDING OFFICIAL SHALL HAVE THE
 AUTHORITY TO REQUIRE THE ELIMINATION OF CONDITIONS
 DEEMED DANGEROUS. THIS NOTE HOLDS TRUE FOR ALL OF
 COMMENTS 7A- 7_.
  
 7B) PLEASE NOTE SHEET 005-A0.03 CODE ANALYSIS UNDER THE
 HEADING CODE RESEARCH APPLICABLE CODES. THE DESIGNER OF
 RECORD LIST THE APPLICABLE CODES 2017 FBC-EB CHAPTER 4
 PRESCRIPTIVE COMPLIANCE METHOD AND CHAPTER 12 HISTORIC
 BUILDINGS. ON THE LEFT SIDE OF THE SAME PAGE THE WORK
 AREA METHOD, LEVEL 2, LEVEL 3 CHANGE OF OCCUPANCY 10
 WHICH IS UNDER THE WORK AREA METHOD OF COMPLIANCE,
 PLEASE CLARIFY TO WHAT DESIGN METHOD (EXISTING BUILDING
 CODE) THIS PROJECT IS TO BE DESIGNED AND COMPLY?
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. THIS
 REVIEW WILL BE ACCOMPLISHED UNDER THE 2017 FBC-EB
 CHAPTER 4 PRESCRIPTIVE COMPLIANCE METHOD AND CHAPTER 12
 HISTORIC BUILDINGS AND THE 2017 FBC-BUILDING WHERE
 DIRECTED BY CHAPTER 4 PRESCRIPTIVE COMPLIANCE METHOD.
  
 7C) PLEASE NOTE SHEET 005-A0.03 CODE ANALYSIS UNDER THE
 HEADING OCCUPANCY DATA ROOMS 201 BALLROOM, & ROOM 202
 UNDER STAGE ARE TO IN THE SAME ROOM. BALLROOM LENDS ONE
 TO BELIEVE THERE WILL BE DANCING IN THIS ROOM. IN THE
 OCCUPANCY TABLE CHART LIST TABLE 1004.1.2 WITH ASSEMBLY
 UNCONCENTRATED 1/15 NET.
 PLEASE REVIEW TABLE 1004.1.2 OF THE 2017 FBC-B 15 SQ.
 FT. WOULD BE USED FOR TABLES AND CHAIRS, 7 SQ. FT.
 WOULD BE USED FOR CHAIRS ONLY, & 5 SQ. FT. WOULD BE
 USED FOR STANDING. IT WOULD APPEAR THAT DANCING WOULD
 BE THE CLOSEST FIT TO THE USAGE AND 5 SQ. FT. SHOULD BE
 USED FOR THE CODE ANALYSIS FOR THE 2ND FLOOR.
  
 7D) THIS WILL TRIPLE THE OCCUPANT LOAD PLEASE PROVIDE A
 NEW ANALYSIS FOR THIS FLOOR FOR EXITING. PLEASE SHOW
 HOW THE OCCUPANTS WILL EXIT SHOW THE EXITING FOR THIS
 FLOOR AND THE ADDITIONAL LOAD FROM THE MEZZANINE. THE
 MEZZANINE OCCUPANT LOAD IS FIGURED IN WITH THE 2ND
 FLOOR OCCUPANT LOAD FOR EXITING. PLEASE PROVIDE THE
 TOTAL OCCUPANT LOAD FOR THE 2ND FLOOR WITH MEZZANINE
 OCCUPANT LOAD. FBC-B 1019.1. 2017 FBC-B 505.2.2 MEANS
 OF EGRESS. THE MEANS OF EGRESS FOR MEZZANINES SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF CHAPTER 10.
  
 7E) SINCE THE 2017 FBC-B SECTION 1019.3 (MEZZANINE
 LEVEL & 2ND FLOOR) DOES ALLOW FOR OPEN STAIRS (EXIT
 ACCESS STAIRWAYS) FOR 2 STORIES:
 1019.3. (1). EXIT ACCESS STAIRWAYS AND RAMPS THAT SERVE
 OR ATMOSPHERICALLY COMMUNICATE BETWEEN ONLY TWO
 STORIES. SUCH INTERCONNECTED STORIES SHALL NOT BE OPEN
 TO OTHER STORIES. PLEASE SHOW HOW EXITING IS TO OCCUR
 WITH NOT GOING THROUGH THE NEW 3 STORY ADDITION.
  
 7F) MEANS OF EGRESS HEADING. FOR THE MEZZANINE LEVEL
 AND 2ND FLOOR, PLEASE SHOW THE TRAVEL DISTANCE FROM THE
 MOST REMOTE POINT ON THE MEZZANINE LEVEL TO AN EXIT,
 SHOW COMPLIANCE WITH EXIT ACCESS TRAVEL DISTANCE IN
 ACCORDANCE WITH
 2017 FBC-B TABLE 1017.2 ASSEMBLY OCCUPANCY, 250 FEET/
 FIRE SPRINKLERED BUILDING.
  
 7G) THE CODE ANALYSIS SHEET A0.03 UNDER THE HEADING
 MEANS OF EGRESS HAS TAKEN A FACTOR OF 0.2? PER OCCUPANT
 FOR STAIRS AND A FACTOR OF 0.15? FOR OTHER MEANS OF
 EGRESS OTHER COMPONENT WIDTHS. THIS EXCEPTION IS FROM
 THE 2017 FBC-B SECTION 1005.3.1 EXCEPTION 1. THE
 EXCEPTION STATES: IN BUILDINGS EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE
 WITH SECTION 903.3.1.1 OR 903.3.1.2 AND AN EMERGENCY
 VOICE/ALARM COMMUNICATION SYSTEM IN ACCORDANCE WITH
 SECTION 907.5.2.2. IN THIS SET OF DOCUMENTS SUBMITTED
 YOU ARE TAKING THE EXCEPTION BUT NO PLANS WERE
 SUBMITTED FOR THE EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 7H) THE CODE ANALYSIS SHEET A0.03 UNDER THE HEADING
 MEANS OF EGRESS LIST UNDER THE STAIR REQUIREMENT A
 SINGLE STAIR AND THE SAME FOR DOORWAYS/ EXITS A SINGLE
 DOOR WAY AS MEETING THE WIDTH REQUIREMENTS. WHEN AN
 OCCUPANT LOAD IS MORE THAN 49 THERE IS REQUIRED 2 MEANS
 OF EGRESS SEE TABLE 1006.1.2 OF THE 2017 FBC-B.
  
 7I) (1) THE CODE ANALYSIS SHEET A0.03 UNDER THE HEADING
 MEANS OF EGRESS LIST UNDER THE STAIR REQUIREMENT
 MINIMUM WIDTH LIST THE FBC 1009.4. PLEASE NOTE THIS IS
 AN OLD CODE SECTION. UNDER THE 2017 FBC-B SECTION
 1011.2 IS WIDTH AND CAPACITY.
  
 7I) (2) THE CODE ANALYSIS SHEET A0.03 UNDER THE HEADING
 MEANS OF EGRESS LIST UNDER THE STAIR REQUIREMENT
 MINIMUM STAIR WIDTH LIST < 50 OCCUPANTS = 36 INCH
 STAIRS (AT MEZZANINE STAIRS). PLEASE BE AWARE IN THE
 2015 IBC COMMENTARY SECTION 1011.2 EXCEPTION 1 STATES:
 THE USE OF THIS EXCEPTION IS LIMITED TO BUILDINGS WHERE
 THE ENTIRE OCCUPANT LOAD OF EACH UPPER STORY AND / OR
 BASEMENT IS LESS THAN 50.
  
 7J) THE CODE ANALYSIS LIST THE EXISTING 3RD FLOOR A R2
 RESIDENTIAL MEZZANINE. SHEET 053-A1.01 LIST THE
 BUILDING AREAS. THE 2ND FLOOR OF THE EXISTING BUILDING
 IS GIVEN AS 4,670 SQ. FT. AND THE EXISTING MEZZANINE
 STAGE AS 2,530 SQ. FT. EQUALS 0.54 PERCENT OF THE 2ND
 FLOOR. MY CALCULATIONS FOR THE 2ND FLOOR ARE 41X89=
 3,649 SQ. FT. AND FOR THE MEZZANINE WITHOUT STAIRS
 BEING DEDUCTED ARE 2,284 SQ. FT. OR 0.62 % OF THE 2ND
 FLOOR, THIS MAKES THE 3RD LEVEL A 3RD FLOOR NOT A
 MEZZANINE WITH A 2 STORY ATRIUM BETWEEN THE 2ND FLOOR
 AND 3RD FLOOR. PLEASE NOTE IF THERE ARE OPEN STAIRS
 THAT COMMUNICATE WITH THE 1ST FLOOR THEN THERE IS A 3
 STORY ATRIUM THAT WOULD COMMUNICATE.
  
 7K) PLEASE NOTE IN THE 2017 FBC DECLARING A BUILDING
 TYPE III-B IS THE EQUIVALENT TO A BUILDING TYPE V IN
 THE 1935 WEST PALM BEACH BUILDING CODE. SECTION 2202.
 TYPE V BUILDINGS SHALL NOT EXCEED A HEIGHT OF 35 FEET
 IN HEIGHT IN WHICH THERE MAY BE NO MORE THAN 2 I/2
 STORIES.
 1935 DEFINITION FOR: HEIGHT OF BUILDING. IS THE
 VERTICAL DISTANCE FROM THE GRADE TO THE HIGHEST POINT
 OF THE COPING OF A FLAT ROOFED BUILDING TO THE DECK
 LINE OF A MANSARD ROOF OR TO THE AVERAGE HEIGHT OF THE
 HIGHEST GABLE OF A PITCH OR HIP ROOF.
  
 7L) PLEASE ALSO NOTE IN THE 1035 WEST PALM BEACH
 BUILDING CODE, THE CODE ONLY MAKES MENTION OF
 MEZZANINES IN BUILDING TYPES I AND II BUILDINGS. WHICH
 IN THE 2017 FBC-B WOULD BE TYPE I-A AND I-B TYPE
 BUILDINGS.
 PLEASE ALSO NOTE THAT UNDER THE 1935 CODE TYPE II
 CONSTRUCTION WAS HEAVY TIMBER BUILDINGS COULD BE UP TO
 65 FEET IN HEIGHT, 5 STORIES, (HEAVY TIMBER BUILDINGS
 CANNOT EXCEED ONE STORY) ROOF CONSTRUCTION HEAVY
 TIMBER, FLOORS AND NON-BEARING PARTITIONS MAYBE OF
 WOOD.
  
 8) STAIR SHAFTS & ELEVATOR SHAFTS:
 8A) STAIR 126 ON THE 2ND FLOOR AND 3RD FLOOR THERE ARE
 DUCTS PENETRATING THE STAIRWELL SHAFT WITH A A/C VENT.
 SEE SHEETS 096-M-102 AND 097-M-103. PLEASE REVIEW:
  
 2017 FBC-B 1023.5 PENETRATIONS. PENETRATIONS INTO OR
 THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT VENTILATION OR PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR
 FIRE DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL
 RACE-WAY SERVING THE INTERIOR EXIT STAIRWAY AND RAMP
 AND TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 714. THERE SHALL NOT BE
 PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT
 STAIRWAYS.
  
 8B) SHEET 097-M-103 IN THE ELEV. F1 THERE APPEARS TO BE
 A 4 INCH DIAMETER SUPPLY THAT DUMPS INTO THE ELECTRIC
 ROOM 315. PLEASE REVIEW THE 2017 FBC-B SECTIONS:
 FBC-B 3002.1 HOISTWAY ENCLOSURE PROTECTION. ELEVATOR
 ENCLOSURES SHALL BE SHAFT ENCLOSURES COMPLYING WITH
 SECTION 713.
  
 FBC-B 713.8.1 PROHIBITED PENETRATIONS. PENETRATIONS
 OTHER THAN THOSE NECESSARY FOR THE PURPOSE OF THE SHAFT
 SHALL NOT BE PERMITTED IN SHAFT ENCLOSURES.
  
 8C)(1) SHEET 056-A1.04 STAIR 126 NOTE # 3 INDICATES THE
 USE OF A ROOF HATCH, SHEET 081-A4.10 STAIR 126 DETAIL
 NO. 7 ALSO SHOWS THE ROOF HATCH. 2017 FBC-B 1023.5
 PENETRATIONS. PENETRATIONS INTO OR THROUGH INTERIOR
 EXIT STAIRWAYS AND RAMPS ARE PROHIBITED EXCEPT FOR
 EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 VENTILATION OR PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACE-WAY SERVING
 THE INTERIOR EXIT STAIRWAY AND RAMP AND TERMINATING AT
 A STEEL BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2).
 SUCH PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL NOT BE PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS.
  
 8C)(2) SHEET 056-A1.04 STAIR 126 NOTE # 3 INDICATES THE
 USE OF A ROOF HATCH, SHEET 081-A4.10 STAIR 126 DETAIL
 NO. 7 ALSO SHOWS THE ROOF HATCH. PLEASE NOTE DOOR
 SCHEDULE FOUND ON SHEET 090-A6.02 INDICATES A DOOR #
 401 A BILCO (NOA 14-0708.07) TYPE S ROOF HATCH. PLEASE
 REVIEW 3 OF 10 OF THIS PRODUCT APPROVAL FOR CLEAR
 OPENING SIZE AND COMPLIANCE WITH FBC-B 1011.12.2 ROOF
 ACCESS EXCEPTION. IN BUILDINGS WITHOUT OCCUPIED ROOFS,
 ACCESS TO THE ROOF SHALL BE PERMITTED TO BE A ROOF
 HATCH OR TRAPDOOR NOT LESS THAN 16 SQUARE FEET IN AREA
 AND HAVING A MINIMUM DIMENSION OF 2 FEET.
  
 9) SHEET 056-A1.04 DETAIL # 2 INDICATES THE USE OF A
 CONCRETE PAVER PEDESTAL SYSTEM.
  
 9A) PLEASE INDICATE WHERE THE APPROVED ROOF COVERING IS
 IN THIS DETAIL. THE DETAIL SHOWS CONCRETE PLANK
 STRUCTURAL ROOF DECK SYSTEM, 2 INCH RIGID BOARD
 INSULATION, LIGHTWEIGHT CONCRETE TOPPING, SLOPED TO
 ROOF DRAINS, AND PEDESTAL CONCRETE PAVER SYSTEM?
  
 2017 FBC-B 1503.1. ROOF DECKS SHALL BE COVERED WITH
 APPROVED ROOF COVERINGS SECURED TO THE BUILDING OR
 STRUCTURE IN ACCORDANCE WITH THE PROVISIONS OF THIS
 CHAPTER. ROOF COVERINGS SHALL BE DESIGNED AND INSTALLED
 IN ACCORDANCE WITH THIS CODE AND THE APPROVED
 MANUFACTURER?S INSTRUCTIONS SUCH THAT THE ROOF COVERING
 SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE.
  
 9B) PLEASE SUBMIT THE PRODUCT APPROVAL FOR THE CONCRETE
 PAVER PEDESTAL SYSTEM AND THAT WAS TESTED FOR THIS TYPE
 OF INSTALLATION ONTO LIGHTWEIGHT CONCRETE. 107.2.1.2
 ADDITIONAL INFORMATION REQUIRED.
 2017 FBC-B 1609.5.2 ROOF COVERINGS. ROOF COVERINGS
 SHALL COMPLY WITH SECTION 1609.5.1.
  
 1609.5.1 ROOF DECK. THE ROOF DECK SHALL BE DESIGNED TO
 WITHSTAND THE WIND PRESSURES DETERMINED IN ACCORDANCE
 WITH ASCE 7.
  
 10) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN
 SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND
 REQUIRED DOCUMENTATION. A COMPLETE REVIEW DID NOT OCCUR
 IN THE 1ST REVIEW CYCLE, WITH THE NEXT PLAN REVIEW
 CYCLE THERE MAYBE ADDITIONAL NEW REVIEW COMMENTS
 BECAUSE OF, PORTIONS OF PLANS NOT REVIEWED, NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 11) - DIGITAL SUBMITTALS: PLANS WILL BE REVIEWED BY THE
 PBC IMPACT FEE OFFICE DIGITALLY VIA PROJECT DOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  