Plan Review Notes
Plan Review Notes For Permit 18110075
Permit Number 18110075
Review Stop E
Sequence Number 1
Notes
Date Text
2018-11-15 13:53:51FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ACCORDING TO THE ORIGINAL PLANS PANEL "B" SUBFED PANEL
 "C"
  
 NOT ALL ACS WHERE INSTALLED IN "B" PLEASE SUBMIT PANEL
 SCHEDULES FOR PANEL "B" FOR COMPARISON.
 IF AC LOADS ARE ALL LOCATED IN PANEL "B PLEASE SUBMIT A
 PANEL "A" PANEL SCHEDULE.