2019-04-09 16:19:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110056
 4/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: PROVIDE SPECIFICATIONS FOR INTERIOR AND
 EXTERIOR DUCTWORK, AND SUPPORT AND HANGING DETAILS PER
 SMACNA STANDARDS- SECTION 603 FBC M.
  
 2) M1: PROVIDE ENGINEERED DETAILS FOR INSTALLATION OF
 THE TRANE PACKAGED UNIT- SECTION 301.15 FBC M.
  
 3) M1: INDICATE THE TYPE AND SIZE OF RETURN GRILL
 CONNECTED TO THE MAIN 24X24 RETURN TRUNK- SECTION 603
 FBC M.
  
 4) M1: INDICATE THE TYPE AND SIZE OF TOILET EXHAUST
 DUCT AND SHOW THE RUN AND TERMINATION LOCATION- SECTION
 501.3.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
  