Date |
Text |
2018-11-06 13:21:37 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. PROJECTS OVER 25 PAGES ARE TO BE SUBMITTED |
| DIGITALLY. CONTACT [email protected], [email protected] |
| FOR MORE INFORMATION. |
| |
| 2. IS THIS A THRESHOLD BUILDING? SEE 553.79(5). ALL |
| PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT REQUIRED |
| BY FS553.79(7)(D). |
| |
| (D)ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS |
| AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| THIS CHAPTER 553 AND CHAPTER 633. |
| |
| IT IS POSSIBLE THAT WIND IMPORTANCE FACTOR AND WIND |
| SPEED IS NOT CORRECT; THIS CANNOT BE REVIEWED DUE TO |
| INSUFFICIENT INFORMATION. |
| |
| 2. A REVIEW CANNOT BE DONE AT THIS TIME. ONLY |
| STRUCTURAL PAGES FOR A STEEL BUILDING WERE SUBMITTED AS |
| WELL AS A SITE PLAN (WHICH IS NOT SIGNED AND SEALED AS |
| REQUIRED). FMEP PAGES, INFORMATION SUCH AS OCCUPANCY |
| CLASSIFICATION, BUILDING TYPE, FLOOR PLAN, ETC. WERE |
| NOT SUBMITTED. |
| |
| PLEASE SEE FBC 107.3.5: |
| |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY |
| THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING |
| MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; |
| SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR |
| TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS; |
| FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL |
| EXTERIOR ELEVATIONS: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 1. SITE REQUIREMENTS: |
| PARKING |
| FIRE ACCESS |
| VEHICLE LOADING |
| DRIVING/TURNING RADIUS |
| FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV) |
| SET BACK/SEPARATION (ASSUMED PROPERTY LINES) |
| LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES |
| FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD |
| ELEVATIONS |
| PROPOSED ELEVATION CERTIFICATE FOR STRUCTURES IN A |
| SPECIAL FLOOD HAZARD AREA |
| 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE SECTION 503). |
| 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| INCLUDE THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| FIRE BLOCKING AND DRAFT STOPPING AND CALCULATED FIRE |
| RESISTANCE |
| 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| EARLY WARNING SMOKE EVACUATION SYSTEMS |
| SCHEMATIC FIRE SPRINKLERS |
| STANDPIPES |
| PRE-ENGINEERED SYSTEMS |
| RISER DIAGRAM |
| 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| INCLUDE THE FOLLOWING |
| REQUIREMENTS: |
| OCCUPANT LOAD AND EGRESS CAPACITIES |
| EARLY WARNING |
| SMOKE CONTROL |
| STAIR PRESSURIZATION |
| SYSTEMS SCHEMATIC |
| 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| DOORS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| SPECIFIC OCCUPANCY REQUIREMENTS |
| CONSTRUCTION REQUIREMENTS |
| HORIZONTAL EXITS/EXIT PASSAGEWAYS |
| 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| SOIL CONDITIONS/ANALYSIS |
| TERMITE PROTECTION |
| DESIGN LOADS |
| WIND REQUIREMENTS |
| BUILDING ENVELOPE |
| STRUCTURAL CALCULATIONS (IF REQUIRED) |
| FOUNDATION |
| FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612, |
| INCLUDING LOWEST FLOOR |
| ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT |
| MATERIALS |
| WALL SYSTEMS |
| FLOOR SYSTEMS |
| ROOF SYSTEMS |
| THRESHOLD INSPECTION PLAN |
| STAIR SYSTEMS |
| 9. MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM |
| INCLUDE THE FOLLOWING: |
| WOOD |
| STEEL |
| ALUMINUM |
| CONCRETE |
| PLASTIC |
| GLASS |
| MASONRY |
| GYPSUM BOARD AND PLASTER |
| INSULATING (MECHANICAL) |
| ROOFING |
| INSULATION |
| 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| FOLLOWING: |
| SITE REQUIREMENTS |
| ACCESSIBLE ROUTE |
| VERTICAL ACCESSIBILITY |
| TOILET AND BATHING FACILITIES |
| DRINKING FOUNTAINS |
| EQUIPMENT |
| SPECIAL OCCUPANCY REQUIREMENTS |
| FAIR HOUSING REQUIREMENTS |
| 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| LIGHT AND VENTILATION |
| SANITATION |
| 12. SPECIAL SYSTEMS: |
| ELEVATORS |
| ESCALATORS |
| LIFTS |
| 13. LOCATION AND INSTALLATION DETAILS. THE SPECIFIC |
| LOCATION AND INSTALLATION DETAILS OF EACH |
| FIRE DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER |
| SHALL BE SHOWN AND PROPERLY |
| IDENTIFIED ON THE BUILDING PLANS BY THE DESIGNER |
| 107.3.5.1.2 ELECTRICAL |
| 1. ELECTRICAL: |
| WIRING |
| SERVICES |
| FEEDERS AND BRANCH CIRCUITS |
| OVERCURRENT PROTECTION |
| GROUNDING |
| WIRING METHODS AND MATERIALS |
| GFCLS |
| 2. EQUIPMENT |
| 3. SPECIAL OCCUPANCIES |
| 4. EMERGENCY SYSTEMS |
| 5. COMMUNICATION SYSTEMS |
| 6. LOW VOLTAGE |
| 7. LOAD CALCULATIONS |
| 8. DESIGN FLOOD ELEVATION |
| 107.3.5.1.3 PLUMBING |
| 1. MINIMUM PLUMBING FACILITIES |
| 2. FIXTURE REQUIREMENTS |
| 3. WATER SUPPLY PIPING |
| 4. SANITARY DRAINAGE |
| 5. WATER HEATERS |
| 6. VENTS |
| 7. ROOF DRAINAGE |
| 8. BACK FLOW PREVENTION |
| 9. IRRIGATION |
| 10. LOCATION OF WATER SUPPLY LINE |
| 11. GREASE TRAPS |
| 12. ENVIRONMENTAL REQUIREMENTS |
| 13. PLUMBING RISER |
| 14. DESIGN FLOOD ELEVATION |
| 107.3.5.1.4 MECHANICAL |
| 1 . ENERGY CALCULATIONS |
| 2 . EXHAUST SYSTEMS: |
| CLOTHES DRYER EXHAUST |
| KITCHEN EQUIPMENT EXHAUST |
| SPECIALTY EXHAUST SYSTEMS |
| 3. EQUIPMENT |
| 4. EQUIPMENT LOCATION |
| 5. MAKE-UP AIR |
| 6. ROOF-MOUNTED EQUIPMENT |
| 7. DUCT SYSTEMS |
| 8. VENTILATION |
| 9. COMBUSTION AIR |
| 10. CHIMNEYS, FIREPLACES AND VENTS |
| 11. APPLIANCES |
| 12. BOILERS |
| 13. REFRIGERATION |
| 14. BATHROOM VENTILATION |
| 15. LABORATORY |
| 16. DESIGN FLOOD ELEVATION |
| 107.3.5.1.5 GAS |
| 1. GAS PIPING |
| 2. VENTING |
| 3. COMBUSTION AIR |
| 4. CHIMNEYS AND VENTS |
| 5. APPLIANCES |
| 6. TYPE OF GAS |
| 7. FIREPLACES |
| 8. LP TANK LOCATION |
| 9. RISER DIAGRAM/SHUTOFFS |
| 10. DESIGN FLOOD ELEVATION |
| 107.3.5.1.6 ENERGY CALCULATIONS |
| 107.3.5.2 DEMOLITION |
| 1. ASBESTOS REMOVAL |
| 2. UTILITY RELEASES |
| 3. PEST CONTROL CERTIFICATION |
| |