Plan Review Notes
Plan Review Notes For Permit 18110056
Permit Number 18110056
Review Stop I
Sequence Number 1
Notes
Date Text
2018-11-06 13:21:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROJECTS OVER 25 PAGES ARE TO BE SUBMITTED
 DIGITALLY. CONTACT [email protected], [email protected]
 FOR MORE INFORMATION.
  
 2. IS THIS A THRESHOLD BUILDING? SEE 553.79(5). ALL
 PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT REQUIRED
 BY FS553.79(7)(D).
  
 (D)ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER 553 AND CHAPTER 633.
  
 IT IS POSSIBLE THAT WIND IMPORTANCE FACTOR AND WIND
 SPEED IS NOT CORRECT; THIS CANNOT BE REVIEWED DUE TO
 INSUFFICIENT INFORMATION.
  
 2. A REVIEW CANNOT BE DONE AT THIS TIME. ONLY
 STRUCTURAL PAGES FOR A STEEL BUILDING WERE SUBMITTED AS
 WELL AS A SITE PLAN (WHICH IS NOT SIGNED AND SEALED AS
 REQUIRED). FMEP PAGES, INFORMATION SUCH AS OCCUPANCY
 CLASSIFICATION, BUILDING TYPE, FLOOR PLAN, ETC. WERE
 NOT SUBMITTED.
  
 PLEASE SEE FBC 107.3.5:
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY
 THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING
 MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 SITE PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR
 TRUSS LAYOUT; ALL FENESTRATION PENETRATIONS;
 FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL
 EXTERIOR ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 PROPOSED ELEVATION CERTIFICATE FOR STRUCTURES IN A
 SPECIAL FLOOD HAZARD AREA
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE SECTION 503).
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFT STOPPING AND CALCULATED FIRE
 RESISTANCE
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING
 SMOKE CONTROL
 STAIR PRESSURIZATION
 SYSTEMS SCHEMATIC
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
 HORIZONTAL EXITS/EXIT PASSAGEWAYS
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 FOUNDATION
 FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612,
 INCLUDING LOWEST FLOOR
 ELEVATIONS, ENCLOSURES, FLOOD DAMAGE-RESISTANT
 MATERIALS
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
 THRESHOLD INSPECTION PLAN
 STAIR SYSTEMS
 9. MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM
 INCLUDE THE FOLLOWING:
 WOOD
 STEEL
 ALUMINUM
 CONCRETE
 PLASTIC
 GLASS
 MASONRY
 GYPSUM BOARD AND PLASTER
 INSULATING (MECHANICAL)
 ROOFING
 INSULATION
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
 SPECIAL OCCUPANCY REQUIREMENTS
 FAIR HOUSING REQUIREMENTS
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
 12. SPECIAL SYSTEMS:
 ELEVATORS
 ESCALATORS
 LIFTS
 13. LOCATION AND INSTALLATION DETAILS. THE SPECIFIC
 LOCATION AND INSTALLATION DETAILS OF EACH
 FIRE DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER
 SHALL BE SHOWN AND PROPERLY
 IDENTIFIED ON THE BUILDING PLANS BY THE DESIGNER
 107.3.5.1.2 ELECTRICAL
 1. ELECTRICAL:
 WIRING
 SERVICES
 FEEDERS AND BRANCH CIRCUITS
 OVERCURRENT PROTECTION
 GROUNDING
 WIRING METHODS AND MATERIALS
 GFCLS
 2. EQUIPMENT
 3. SPECIAL OCCUPANCIES
 4. EMERGENCY SYSTEMS
 5. COMMUNICATION SYSTEMS
 6. LOW VOLTAGE
 7. LOAD CALCULATIONS
 8. DESIGN FLOOD ELEVATION
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 7. ROOF DRAINAGE
 8. BACK FLOW PREVENTION
 9. IRRIGATION
 10. LOCATION OF WATER SUPPLY LINE
 11. GREASE TRAPS
 12. ENVIRONMENTAL REQUIREMENTS
 13. PLUMBING RISER
 14. DESIGN FLOOD ELEVATION
 107.3.5.1.4 MECHANICAL
 1 . ENERGY CALCULATIONS
 2 . EXHAUST SYSTEMS:
 CLOTHES DRYER EXHAUST
 KITCHEN EQUIPMENT EXHAUST
 SPECIALTY EXHAUST SYSTEMS
 3. EQUIPMENT
 4. EQUIPMENT LOCATION
 5. MAKE-UP AIR
 6. ROOF-MOUNTED EQUIPMENT
 7. DUCT SYSTEMS
 8. VENTILATION
 9. COMBUSTION AIR
 10. CHIMNEYS, FIREPLACES AND VENTS
 11. APPLIANCES
 12. BOILERS
 13. REFRIGERATION
 14. BATHROOM VENTILATION
 15. LABORATORY
 16. DESIGN FLOOD ELEVATION
 107.3.5.1.5 GAS
 1. GAS PIPING
 2. VENTING
 3. COMBUSTION AIR
 4. CHIMNEYS AND VENTS
 5. APPLIANCES
 6. TYPE OF GAS
 7. FIREPLACES
 8. LP TANK LOCATION
 9. RISER DIAGRAM/SHUTOFFS
 10. DESIGN FLOOD ELEVATION
 107.3.5.1.6 ENERGY CALCULATIONS
 107.3.5.2 DEMOLITION
 1. ASBESTOS REMOVAL
 2. UTILITY RELEASES
 3. PEST CONTROL CERTIFICATION
  