Plan Review Notes
Plan Review Notes For Permit 18110056
Permit Number 18110056
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-03-14 11:15:43PERMIT # 18110056
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PERMIT APPLICATION STATES THAT THE PERMIT IS FOR THE
 CONSTRUCTION OF A 5900 SQ FT STRUCTURE, HOWEVER NOT
 ENOUGH DETAILS REGARDING THE STRUCTURE HAVE BEEN
 PROVIDED.
  
 2) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
 3) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 4) ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]