Plan Review Notes
Plan Review Notes For Permit 18110051
Permit Number 18110051
Review Stop B
Sequence Number 3
Notes
Date Text
2018-11-28 18:55:08RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS
  
 ORIGINAL COMMENT:
 1) THIS ONE STORY STRUCTURE IS LOCATED IN EXPOSURE
 CATEGORY D. THE REQUIRED UPLIFT PRESSURE FOR THE FLAT
 ROOF IS -116 PSF FOR ROOF ZONE 3 FOR A STRUCTURE WITH A
 15 FT. MEAN ROOF HEIGHT EXCEEDS THE -97.5 PSF FOR
 SYSTEM NO. W-19 THAT WAS SELECTED FROM FL16027-R2.
 SUBMIT PRODUCT APPROVALS THAT MEET THE REQUIRED UPLIFT.
 FBC-R301.2.1
  
 RESPONSE:
 NEW FLAT ROOF ASSEMBLY W-5 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES EITHER. DESIGN PRESSURES
 ARE EVEN LOWER THAN THE ASSEMBLY SELECTED ON THE FIRST
 SUBMITTAL. NEED TO SELECT ASSEMBLY THAT MEETS THE
 DESIGN PRESSURES FOR ALL ROOF ZONES. NOTE: BONDED
 ASSEMBLIES DON'T ALLOW RATIONAL ANALYSIS (RAS 117
 CALCULATIONS FOR NAIL ENHANCEMENT). SEE NOTE #10 ON
 PAGE 2 OF 26 OF PRODUCT APPROVAL FL16027-R2 SUBMITTED.
  
 ORIGINAL COMMENT:
 2) THE UNDERLAYMENT AND CAP SHEET SPECIFIED ON PAGE 4
 OF ROOFING FORM 100, DO NOT MATCH THE ONES THAT WERE
 MARKED ON THE PRODUCT APPROVAL FL16027. PLEASE CORRECT.
 FBC 107.2.1
  
 RESPONSE:
 INFORMATION SUBMITTED IS NOT CLEAR. SEC. 107.2.1 CITY
 AMENDMENTS.
 WHAT'S CAP SHEET SA-P? AND WHAT'S OTHER UNDERLAYMENT
 SA-V ?.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]