2018-11-01 16:26:07 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THIS ONE STORY STRUCTURE IS LOCATED IN EXPOSURE | | CATEGORY D. THE REQUIRED UPLIFT PRESSURE FOR THE FLAT | | ROOF OF -116 PSF FOR ROOF ZONE 3 FOR A STRUCTURE WITH A | | 15 FT. MEAN ROOF HEIGHT EXCEEDS THE -97.5 PSF FOR | | SYSTEM NO. W-19 THAT WAS SELECTED FROM FL16027-R2. | | SUBMIT PRODUCT APPROVALS THAT MEET THE REQUIRED UPLIFT. | | FBC-R301.2.1 | | | | 2) THE UNDERLAYMENT AND CAP SHEET SPECIFIED ON PAGE 4 | | OF ROOFING FORM 100, DO NOT MATCH THE ONES THAT WERE | | MARKED ON THE PRODUCT APPROVAL FL16027. PLEASE CORRECT. | | FBC 107.2.1 |
|