Plan Review Notes
Plan Review Notes For Permit 18110051
Permit Number 18110051
Review Stop B
Sequence Number 1
Notes
Date Text
2018-11-01 16:26:07PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS ONE STORY STRUCTURE IS LOCATED IN EXPOSURE
 CATEGORY D. THE REQUIRED UPLIFT PRESSURE FOR THE FLAT
 ROOF OF -116 PSF FOR ROOF ZONE 3 FOR A STRUCTURE WITH A
 15 FT. MEAN ROOF HEIGHT EXCEEDS THE -97.5 PSF FOR
 SYSTEM NO. W-19 THAT WAS SELECTED FROM FL16027-R2.
 SUBMIT PRODUCT APPROVALS THAT MEET THE REQUIRED UPLIFT.
 FBC-R301.2.1
  
 2) THE UNDERLAYMENT AND CAP SHEET SPECIFIED ON PAGE 4
 OF ROOFING FORM 100, DO NOT MATCH THE ONES THAT WERE
 MARKED ON THE PRODUCT APPROVAL FL16027. PLEASE CORRECT.
 FBC 107.2.1