Plan Review Notes For Permit 18110020 |
Permit Number |
18110020 |
|
Review Stop |
Z |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-01-11 09:53:47 | PREVIOUS COMMENTS NOT ADDRESSED: | | | | PLEASE PROVIDE A CERTIFIED BOUNDARY SURVEY. | | | | PLEASE SHOW SETBACK OF GENERATOR FROM PROPERTY LINE. | | GENERATOR CANNOT PROJECT MORE THAN FOUR FEET INTO THE | | REQUIRED REAR SETBACK OF 5'. | | | | GENERATOR MUST BE SCREEND WITH LANDSCAPE ON AT LEAST | | THREE SIDE, MOST IMPORTANTLY FROM THE ROW. PLEASE | | INDICATE LOCATION OF PROPOSED LANDSCAPING. | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | [email protected] | | 561 822 1426 |
|