2019-01-25 10:27:02 | 1) PLANS DRAWN IN PENCIL ARE UNACCEPTABLE. WPB AMEND. |
| TO FBC SEC. 107.2.1. THERE ARE STILL PLANS IN THE |
| PACKAGE THAT ARE DONE IN PENCIL. REMOVE THESE PLANS |
| FROM THE SUBMITTAL PACKAGE.2ND REQUEST. |
| 2) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 |
| FBC-R SEC. G2413.4.1, G2413.4.2.2ND REQUEST. |
| 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, AND |
| ALL PIPE SIZES. WPB AMENDMENTS TO FBC SEC.107.2.1. 2ND |
| REQUEST. |
| 4.) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| G2413.4 (1 ) THROUGH G2413.4 (21).2ND REQUEST. |
| 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER) TO THE MOST REMOTE OUTLET IN THE BUILDING AND / |
| OR SYSTEM PER THE 2017 FBC-FUEL GAS SEC.402.4.1, |
| 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, G2413.4.2. |
| 2ND REQUEST. |
| 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| 2ND REQUEST. |
| 7) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. 2ND REQUEST. |
| 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. 2ND REQUEST. |
| 9) THE PLANS INDICATE AN EXISTING GAS METER AND CITY |
| RECORDS DO NOT SHOW SHOW AN EXISTING GAS SYSTEM FOR |
| THIS ADDRESS. THE EXISTING SYSTEM MUST BE PERMITTED. |
| THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED |
| INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE |
| EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE |
| EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. 2ND |
| REQUEST. 2ND REQUEST. |
| 10) THE GENERATOR EXHAUST SHALL BE LOCATED IN |
| ACCORDANCE WITH THE INSTALLATION MANUAL IN RELATION TO |
| BUILDING OPENINGS INCLUDING SOFFITT VENTS. SHOW THE |
| DISTANCE ON THE PLANS. 2017 FBC-FUEL GAS SEC. 616.1. |
| 2ND REQUEST. |
| 11) ONE COPY OF A SURVEY THAT HAS BEEN SUBMITTED SHOWS |
| THE GENERATOR UP NEAR THE HOUSE NEXT TO THE A/C UNIT |
| AND ANOTHER SURVEY SHOWS THE GENERATOR IN A DIFFERENT |
| LOCATION BUT DOES NOT SHOW THE DISTANCE FROM THE |
| EXTERIOR WALL OF THE STRUCTURE. CLARIFY. WPB AMEND. TO |
| FBC SEC. 107.2.1. . |
| 12) THE GENERATOR SHALL MEET THE REQUIREMENTS OF NFPA |
| 37. THE GENERATOR SPECS DO NOT INDICATE COMPLIANCE. |
| |
| NOTE: ONLY ONE COMMENT FROM THE PREVIOUS REVIEW HAS |
| BEEN ADDRESSED. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |
| |