2019-01-17 13:38:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 ALL PREVIOUS FIRE COMMENTS WERE NOT ADDRESSED:
  
 PLEASE ADDRESS ALL FIRE COMMENTS NOT COMPLIED WITH.
  
  
 1) COMPLIED
  
 THIS INSTALLATION SHALL MEET THE REQUIREMENTS OF NFPA
 37. STANDARD FOR THE INSTALLATION AND USE OF STATIONARY
 COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION
  
 THERE ARE NO INDICATION OR DIMENSIONS OF THE OPENINGS
 ALONG THE WALL OF THE STRUCTURE.
  
 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR
 WEATHERPROOF
 HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS
 SHALL
 BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS
 AND AT
 LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE
 WALLS. A
 MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER
 OF THE
 FOLLOWING CONDITIONS EXIST:
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5
 M (5 FT)
 FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING
 OF
 AT LEAST 1 HOUR.
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE
 MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE
 WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS
 OUTSIDE THE ENCLOSURE.
  
  
 PLEASE INDICATED THE LOCATION AND DIMENSION FROM ALL
 OPENINGS ALONG THE WALL OF THE STRUCTURE.
  
  
  
  
 2) NOT COMPLIED
  
 THERE IS NO INDICATION OR DIMESNION FROM THE PROPERTY
 LINE OR STRUCTURE IN THE ADJACENT STRUCTURE AND THE
 OPEINGS ALONG THAT STRUCTURE.
  
 PLEASE PROVIDE DETAILS OF THE ADJACENT PROPERTY.
  
  
  
  
 3) NOT COMPLIED
  
 THERE IS NO INDICATION OF ANY OVERHANG OR SOFFITT AREA
 OVER THE GENERATOR OF THE COMMERCIAL STRUCTURE IT IS
 NEXT TO.
  
 EXHAUST FUMES MAY ACCUMULATE AND ENTER THE STRUCTURE
 FROM THE OVERHANG OR SOFFITT AREA,
  
  
 8.2.3 EXHAUST SYSTEM TERMINATION.
 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE
 STRUCTURE
 AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF
 COMBUSTION
 WILL DISCHARGE TO A SAFE LOCATION.
 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE
 DIRECTED TOWARD
 COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES
 CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR
 COMBUSTIBLE
 DUSTS.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 4) NOT COMPLIED
  
 THERE IS NO INDICATION IF THE SYSTEM WILL BE SUPPLY
 POWER TO THE EXISTING FIRE ALARM OR FIRE SPRINKLER
 ALARM SYSTEMS.
  
 IF SO, IT SHALL COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION
  
 WILL THIS SYSTEM SUPPLY POWER TO A FIRE ALARM SYSTEM?
  
 PLEASE PROVIDE DETAILS AS TO WHAT CLASS THIS SYSTEM IS
 AND ENSURE COMPLIANCE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 ADDITIONAL COMMENT:
  
  
 7) THERE IS NO ADDRESS ATTACHED TO THE SUBMITTED
 SURVEY.
  
 PLEASE PROVIDE THE CORRECT ADDRESS TO THE SUBMITTED
 SURVEY AND ENSURE ONE FOR COPY EACH SET.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  