Plan Review Notes For Permit 18110020 |
Permit Number |
18110020 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-01-22 15:53:23 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | (COMMENTS FROM FIRST REVIEW WERE NOT ADDRESSED.) | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF SIGNED AND SEALED ENGINEERING FOR | | THE PREFABRICATED GENERATOR PAD THAT IS SPECIFIC TO THE | | MAKE AND MODEL OF GENERATOR THAT WILL BE INSTALLED. FBC | | 1609.1 | | | | 2) SPECIFY THE TYPE, NUMBER AND LOCATION OF ANCHORS | | THAT WILL BE USED TO SECURE THE GENERATOR TO THE | | GENERATOR PAD TO RESIST WIND LOADS. FBC 107.2.1 | | | | 3) SUBMIT TWO SETS OF THE MANUFACTURER'S INSTALLATION | | MANUAL FOR THE GENERATOR. FBC 107.2.1 |
|