2018-11-09 16:37:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. THIS INCLUDES
 SHEETS PROVIDED FOR LOAD CALCULATION, ETC. PROVIDE
 CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THERE ARE TWO DIFFERENT LOAD CALCULATIONS
 PROVIDED IN PACKAGE THAT HAVE DIFFERENT TOTALS. BOTH
 LOAD CALCULATIONS USE DEMAND FACTORS THAT ARE ONLY
 PERMITTED FOR RESIDENTIAL CALCULATIONS AND CANNOT BE
 USED FOR THIS PROJECT. PROVIDE COMMERCIAL LOAD
 CALCULATION. NEC 220
 4. PROVIDE GENERATOR AND TRANSFER SWITCH SIZED TO
 HANDLE THE LOAD CALCULATED IN COMMENT 3. NEC 701.4
 5. PROVIDE ACCURATE RISER DIAGRAM. THE RISER CURRENTLY
 SHOWS A 200 AMP METER/MAIN WITH TWO 100 AMP BREAKERS
 AND ONE 50 AMP BREAKER. WHAT ARE THESE ITEMS FEEDING
 AND HOW WILL A 200 AMP TRANSFER SWITCH BE TIED INTO
 THESE CIRCUITS? WILL THE TRANSFER SWITCH BE THE MAIN?
 IS IT SERVICE ENTRANCE RATED? NEED MORE DETAIL IN RISER
 DIAGRAM. NEC 215.5, NEC 701.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved