Plan Review Notes
Plan Review Notes For Permit 18101448
Permit Number 18101448
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-08 13:16:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. NO INFORMATION WAS PROVIDED - OCCUPANCY
 CLASSIFICATION FBC B CHAPTER 3, RESISTANCE TO WIND
 (BOTH ANCHORING AND THE PROPOSED STRUCTURE), FBC B
 1609. WHAT WILL BE STORED IN THE SHIPPING CONTAINER?
 SHIPPING CONTAINERS ARE DESIGNED TO BE LOADED WITH
 MATERIAL AND SHIPPED, WHICH DOES NOT APPEAR TO BE THE
 PROPOSED USE UNDER THIS PERMIT. IF THIS IS FOR STORAGE
 OF EQUIPMENT (SUCH AS LAWNMOWERS, OTHER MAINTENANCE
 EQUIPMENT), PROVIDE A PLAN WHICH CLEARLY SHOWS PROPOSED
 USE.
  
 PER FS471, ENGINEERING WILL BE REQUIRED TO DEMONSTRATE
 WIND RESISTANCE. IT IS NOT CLEAR IF A DESIGN
 PROFESSIONAL WILL BE REQUIRED FOR OTHER PLANS AS SCOPE
 HAS NOT BEEN DETERMINED.
  
 A SITE PLAN IS REQUIRED SHOWING DISTANCE TO PROPERTY
 LINE AND ASSUMED PROPERTY LINE, SEE FBC B CHAPTERS 6
 AND 7. BUILDING CONSTRUCTION TYPE, OPENINGS, FIRE
 RESISTANCE (IF APPLICABLE) INFORMATION NOT PROVIDED.
  
 CODE REQUIREMENTS CANNOT BE DETERMINED AT THIS TIME DUE
 TO INSUFFICIENT INFORMATION.
  
 2. THIS WAS SUBMITTED AS "489 EXEMPT". UNTIL IT IS
 DETERMINED THAT NO WORK WILL BE REQUIRED, THE PERMIT
 WILL NOT BE ISSUED AS 489 EXEMPT AND LICENSED
 CONTRACTORS WILL BE REQUIRED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS.
  
 3. AN IMPACT FEE ASSESSMENT MAY BE REQUIRED (AND
 BUILDING PERMIT TYPE CHANGED FROM "ZONING" TO
 "BLD-COM").
  
  
  
  
  
  