2018-12-08 13:16:07 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. NO INFORMATION WAS PROVIDED - OCCUPANCY |
| CLASSIFICATION FBC B CHAPTER 3, RESISTANCE TO WIND |
| (BOTH ANCHORING AND THE PROPOSED STRUCTURE), FBC B |
| 1609. WHAT WILL BE STORED IN THE SHIPPING CONTAINER? |
| SHIPPING CONTAINERS ARE DESIGNED TO BE LOADED WITH |
| MATERIAL AND SHIPPED, WHICH DOES NOT APPEAR TO BE THE |
| PROPOSED USE UNDER THIS PERMIT. IF THIS IS FOR STORAGE |
| OF EQUIPMENT (SUCH AS LAWNMOWERS, OTHER MAINTENANCE |
| EQUIPMENT), PROVIDE A PLAN WHICH CLEARLY SHOWS PROPOSED |
| USE. |
| |
| PER FS471, ENGINEERING WILL BE REQUIRED TO DEMONSTRATE |
| WIND RESISTANCE. IT IS NOT CLEAR IF A DESIGN |
| PROFESSIONAL WILL BE REQUIRED FOR OTHER PLANS AS SCOPE |
| HAS NOT BEEN DETERMINED. |
| |
| A SITE PLAN IS REQUIRED SHOWING DISTANCE TO PROPERTY |
| LINE AND ASSUMED PROPERTY LINE, SEE FBC B CHAPTERS 6 |
| AND 7. BUILDING CONSTRUCTION TYPE, OPENINGS, FIRE |
| RESISTANCE (IF APPLICABLE) INFORMATION NOT PROVIDED. |
| |
| CODE REQUIREMENTS CANNOT BE DETERMINED AT THIS TIME DUE |
| TO INSUFFICIENT INFORMATION. |
| |
| 2. THIS WAS SUBMITTED AS "489 EXEMPT". UNTIL IT IS |
| DETERMINED THAT NO WORK WILL BE REQUIRED, THE PERMIT |
| WILL NOT BE ISSUED AS 489 EXEMPT AND LICENSED |
| CONTRACTORS WILL BE REQUIRED. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS. |
| |
| 3. AN IMPACT FEE ASSESSMENT MAY BE REQUIRED (AND |
| BUILDING PERMIT TYPE CHANGED FROM "ZONING" TO |
| "BLD-COM"). |
| |
| |
| |
| |
| |
| |