2018-11-13 10:41:04 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18101440 |
| REVIEWED: NOVEMBER 13, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| |
| 1. [FBC 1505.1]PLEASE PROVIDE THE TYPE OF CONSTRUCTION |
| AND THE FIRE CLASSIFICATION OF NEW ROOF SYSTEM. (UL |
| LISTING?)IF CONSTRUCTION TYPE IS UNKNOWN A CLASS A OR B |
| WILL SATISFY REQUIREMENTS. |
| |
| 2. [FBC 1503.4]ROOF DRAINAGE |
| PROVIDE ROOF DRAIN CALCULATIONS AND DESIGN TO COMPLY |
| WITH SECTIONS 1106 AND 1107, AS APPLICABLE, OF THE |
| FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. |
| HOW DOES DRAINAGE WORK FOR EXISTING ROOF? WHAT IS THE |
| PROPOSED SLOPE? |
| FORM 100 SAYS 3/12, BUT THIS IS A FLAT ROOF. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |