Plan Review Notes
Plan Review Notes For Permit 18101404
Permit Number 18101404
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-11-01 11:06:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PLANS INDICATE THE USE OF FLEX DROP
 PIPING. DOES THE EXISTING SYSTEM HAVE FLEX DROPS? THE
 EXISTING SYSTEM APPEARS TO A TYPICAL ARM OVER AND NOT
 DESIGN FOR THE USE OF FLEX DROPS.
  
 THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS
 THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE
 EXISTING SYSTEM DESIGN.
  
 PLEASE PROVIDE CALCULATIONS DETAILS OR JUSTIFY WITH
 SPECIFIC DETAILS AND CODE REFERENCES.
  
  
  
 2) THERE ARE NO SPEC SHEETS FOR THE TYPE AND/OR SIZE OF
 THE FLEX DROP PIPING.
  
 PLEASE PROVIDE SHEETS THAT MATCH THE NEW HYDRAULIC
 CALCULATIONS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  