Plan Review Notes For Permit 18101404 |
Permit Number |
18101404 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-11-01 11:06:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THE SUBMITTED PLANS INDICATE THE USE OF FLEX DROP | | PIPING. DOES THE EXISTING SYSTEM HAVE FLEX DROPS? THE | | EXISTING SYSTEM APPEARS TO A TYPICAL ARM OVER AND NOT | | DESIGN FOR THE USE OF FLEX DROPS. | | | | THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS | | THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | EXISTING SYSTEM DESIGN. | | | | PLEASE PROVIDE CALCULATIONS DETAILS OR JUSTIFY WITH | | SPECIFIC DETAILS AND CODE REFERENCES. | | | | | | | | 2) THERE ARE NO SPEC SHEETS FOR THE TYPE AND/OR SIZE OF | | THE FLEX DROP PIPING. | | | | PLEASE PROVIDE SHEETS THAT MATCH THE NEW HYDRAULIC | | CALCULATIONS. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|