Plan Review Notes For Permit 18101365 |
Permit Number |
18101365 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-11-02 10:49:58 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) SHEET A 4 & E 2.1 - THERE ARE NO INDICATIONS OF FIRE | | ALARM BEING SUBMITTED UNDER SEPARATE SHOP DEAWINGS. | | | | PLEASE ENSURE THA ALL FIRE ALARM WORK IS SUBMITTED | | UNDER SEPARATE SHOP DRAWINGS BY LICENSED FIRE ALARM | | CONTRACTORS. | | | | | | | | 2) SHEET M 2.1 - THERE IS AN INDICATION OF A RE WITHIN | | THE NEW FIRE WALL THAT APPEARS TO BE A FD. | | | | PLEASE ENSURE THAT THIS RE IS A FD TO MEET THE RATING | | OF THIS FIRE WALL. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|