2018-12-20 03:32:561) THE FLOOR PLAN LAYOUT ON SHT. LS-101 DOES NOT MATCH
 THE FLOOR PLAN LAYOUT ON SHT. ID-101. ALTHOUGH THE
 SHADED AREA IS NOT IN THE SCOPE OF WORK, THE
 CONFIGURATION/LAYOUT OF TENANT SPACE #2 ON SHEET ID-101
 SHOWS PARTITIONS, CORRIDORS, DOORS AND WHAT APPEARS TO
 BE SINK YET SHEET LS-101 SHOWS NONE OF THIS. CLARIFY.
 2ND REQUEST.
 2) THE PLANS SHALL BEAR THE DIGITAL SIGNATURE AND SEAL
 OF THE DESIGN PROFESSIONAL WHO CREATED THE PLANS. FL.
 ADMIN. CODE RULE 61G1-16.005.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW