Plan Review Notes For Permit 18101337 |
Permit Number |
18101337 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-12-13 08:48:15 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18101337 | | 12/13/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE AC LOAD CALCULATIONS ARE INCORRECTLY LISTING | | MIAMI AS THE PROJECT LOCATION- PLEASE CORRECT. | | | | 2) SHEET M200: THE OUTSIDE AIR CALCULATIONS TABLE IS | | INCORRECTLY INDICATING "CORRIDOR' AS THE VENTILATION | | ZONE FOR RTU-3. PLEASE CHANGE THE ZONE TO READ TENANT | | 2. | | | | 3) M200: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE | | RTU-S PER SECTION 307.2 FBC M. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|