2018-12-13 08:48:151ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18101337
 12/13/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC LOAD CALCULATIONS ARE INCORRECTLY LISTING
 MIAMI AS THE PROJECT LOCATION- PLEASE CORRECT.
  
 2) SHEET M200: THE OUTSIDE AIR CALCULATIONS TABLE IS
 INCORRECTLY INDICATING "CORRIDOR' AS THE VENTILATION
 ZONE FOR RTU-3. PLEASE CHANGE THE ZONE TO READ TENANT
 2.
  
 3) M200: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 RTU-S PER SECTION 307.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  